User manual
Engineering
3.4 STEP 7 V5
SITOP UPS1600 / UPS1100
68 Operating Instructions, 05.2014, C98130-A7628-A1-4-7629
3. Open the "Accessible nodes" window with the "Target system > Display accessible
nodes" menu command.
Note
For an online connection via the "Accessible nodes" window, PG/PC and "Accessible
nodes" must be connected to the same physical Ethernet subnet.
4. Select the "Target system > Update firmware" menu command.
5. In the open "Update firmware" dialog, press the "Browse" button to select the path to the
directory with the unzipped files.
In this directory, select the "dc-ups.upd" file.
6. After you have selected a file, the information in the bottom boxes of the "Update
firmware" dialog box indicate the modules for which the file is suitable and from which
firmware version.
7. Click the "Run" button.
8. STEP 7 verifies that the selected file can be interpreted by the module and then
downloads the file to the module.
9. If this requires changing the operating state of the CPU, you will be prompted to do this in
the relevant dialog boxes.
10.The module then automatically updates the firmware.
Note
A separate connection is established to the CPU for the firmware update, if
available. In
this case, the task can be interrupted. If no resources are available for another
connection, an existing connection will be used automatically. In this case, the task
cannot be interrupted; the "Cancel" button in the transfer dialog is gray
ed-out and cannot
be operated.
11.Use STEP 7 (read out the CPU diagnostics buffer) to verify that the module can start with
the new firmware.