3.4.6
Diagnostics
The following data can be fetched using the Diagnostics function:
Group
Value
UPS1600 general
MLFB number
Serial number
Fetching diagnostics data
You can use the "Station > Open online" menu command in "HW Config" to select the
UPS1600 and view the diagnostics data.
3.4.7
Firmware update
WARNING
The UPS is reset while updating the firmware. For safety reasons, the output is switched
off.
Ensure that no damage is caused to the system and that the PG/PC has a power supply
independent of the UPS during the firmware update.
The files for updating the firmware (firmware updates) are available online under
(http://support.automation.siemens.com/WW/view/de/79207181). Different firmware updates
are offered depending on the amperage of the UPS.
Note
Observe the compatibility of the firmware!
Determine the amperage of your UPS and download the appropriate firmware update. Other
firmware updates are not compatible.
Preconditions
● The UPS1600 has been correctly connected, and connected with the system.
● PG/PC with STEP 7 V5 is connected with the system.
Procedure
1. Download the firmware update.
The firmware update consists of several files grouped in a ZIP file.
2. Unpack the ZIP file into a temporary directory.