3.4 STEP 7 V5
SITOP UPS1600 / UPS1100
Operating Instructions, 05.2014, C98130-A7628-A1-4-7629
65
Web server
Parameter
Value range
Activating a Web server
Yes / No
Set here whether access to the UPS1600 via web server is permitted.
3.4.5
Loading the configuration into the controller (commissioning)
In the delivered state, the UPS1600 has not yet been assigned any IP address and the
DHCP protocol is deactivated.
When the UPS1600 is first connected with a controller, it is assigned a device name and an
IP address by the controller. A new configuration can be loaded to the device using STEP 7
V5 .
Preconditions
The UPS1600 has been correctly connected, and connected with the system.
PG/PC with STEP 7 V5 is connected with the system.
Displaying accessible nodes
Note
If nodes can only be accessed via interposed switches or routers (with protocol conversion),
they are not displayed in the list of the accessible nodes.
1. Click in the "Target system" menu on "Display accessible nodes"
The "Accessible nodes" window is opened with the following displays:
The station
the UPS1600
The following table shows which information is displayed in the "Object name" column.
Accessible nodes
Object name
Description
S7-CPU, PC station Name of the station The "Details" view also shows the operating state, module
type and, if available, information from the associated STEP
7 project (station name, CPU name, system identification).