User manual
Engineering
3.4 STEP 7 V5
SITOP UPS1600 / UPS1100
64 Operating Instructions, 05.2014, C98130-A7628-A1-4-7629
Charging parameters
Parameter
Value range
Default setting
End-of-charge voltage
24 … 30 V
27.3 V
Charge current
1 … 4,000 mA
800 mA
●
End-of-charge voltage (0.01 V)
Note
If UPS1100 batte
ry modules are used, this value does not need to be specified.
The charging completes when the selected end-of-charge voltage is reached.
●
Charge current (mA)
The battery is charged to the maximum with the selected charge current. The
manufacturer's details for the permitted charge current of the battery must be observed. If
several batteries are connected, the smallest permitted charge current applies.
Note
If UPS1100 battery modules are being used, these values do not need to be specified.
The following, device-dependent maximum values also apply:
– SITOP UPS1600 20 A: Maximum permitted charge current 4,000 mA
– SITOP UPS1600 10 A: Maximum permitted charge current 3,000 mA
Reset parameters
Parameter
Value range
Default setting
Reset time (second)
1 … 120 s
5 s
Specify the minimum interruption time for which the output voltage is switched off after the
buffering.
Identification
Parameter
Value range
Contact
Free text
Location
Free text
●
Contact
Enter, for example, a contact address or the name of a staff member.
●
Location
Enter a description of the location that can be used to locate the UPS1600.