User manual

Engineering
3.4 STEP 7 V5
SITOP UPS1600 / UPS1100
Operating Instructions, 05.2014, C98130-A7628-A1-4-7629
63
Buffer time
The time to be buffered by the UPS. The "Buffering allowed" parameter is used to specify
whether buffering should be performed.
Additional buffer time after PC shutdown
Time, to be buffered by the UPS1600 after the PC has been shut down.
Connection threshold
If the connection threshold value is undershot, the UPS starts buffering. If the value of the
connection threshold is reached or undershot again later, the UPS stops buffering.
Stop buffering voltage
The voltage at which battery discharge is terminated.
Wait time for stable input voltage
The time in which no alarm is issued to the system although the connection threshold
was undershot.
Downtime alarm
The time in which no alarm is issued to the system although it is buffered.
Buffering allowed
Select between buffers with the specified values or passive measurement of the power
supply by the UPS.
Enable reset after buffering
If the value is set to "Yes", after the line supply returns during buffering, the system issues
a reset and switches the output off for a defined time. This option is useful, when, for
example, computer networks are protected by the UPS that can be activated by a reset
when the power supply is restored.
Battery parameters
Parameter
Value range
Default setting
Faulty battery voltage
1 … 18 V
6 V
Battery capacity
0.1 … 3,200 Ah
10 Ah
Ignore data of coded battery
Yes / No
No
Faulty battery voltage
If the battery voltage undershoots this value, it is considered as being faulty by the
UPS1600 and not charged.
Battery capacity
If no UPS1100 battery modules are being used: Enter the total capacity of the installed
batteries.
Ignore data of coded battery
Set the value to "Yes" if no UPS1100 battery modules are being used.