3.4 STEP 7 V5
SITOP UPS1600 / UPS1100
62 Operating Instructions, 05.2014, C98130-A7628-A1-4-7629
6. Click the desired subgroup.
The subgroup opens.
7. Enter the values.
8. Confirm your entry by clicking on "OK".
The parameters are stored in the project.
Buffer parameters
Parameter
Value range
Default setting
Buffer time
1 … 32767 s
60 s
Additional buffer time after PC shutdown 1 … 300 s 10 s
Connection threshold
21 … 25 V
21.5 V
Stop buffering voltage
18 … 23 V
18.5 V
Wait time for stable input voltage
5 … 65,000 ms
500 ms
Downtime alarm
0 … 20,000 ms
125 ms
Buffering allowed
Yes / No
Yes
Enable reset after buffering
Yes / No
Yes