User manual

Engineering
3.4 STEP 7 V5
SITOP UPS1600 / UPS1100
Operating Instructions, 05.2014, C98130-A7628-A1-4-7629
61
3.4.3
UPS parameters in STEP 7 V5
The configurable parameters of the UPS are subdivided into six subgroups in STEP 7 V5.
These subgroups are shown in the table below.
Subgroup
Description
Buffer parameters
All parameters that affect the behavior of the UPS for buffering.
Battery parameters
Parameterization of the deployed battery.
Charging parameters Parameters for the charging behavior:
End-of-charge voltage
Charge current
Reset parameters
Activate interruption of the output voltage for supply system restoration.
Identification
Specification of a location and contact details in order to identify the UPS.
Web server
Specification whether access to the UPS via Web server is permitted (yes/no).
A detailed description of the individual parameters of the subgroups is contained in the
associated section under Parameterizing the UPS in STEP 7 V5 (Page 61).
3.4.4
Parameterizing the UPS in STEP 7 V5
The procedure is the same for all parameters. This section describes the general procedure
to reach the configuration dialog. The individual parameters and their possible values are
described in the following subsections.
Each parameter has a start value. A click on "Reset to initial values" resets all parameters of
a subgroup to the associated start value.
Preconditions
The UPS1600 has been integrated in the opened project and networked.
Proceed as follows
1. Open Network view "NetPro" ("Tools > Configure network").
The controller and the networked UPS1600 are displayed.
2. Double-click in the network view on the UPS1600.
3. Open the hardware configuration.
The hardware configuration opens.
4. In the hardware configuration , double-click on the entry of a UPS1600 in the station
window.
5. In the configuration dialog click on the "Parameters" tab.