User manual

Engineering
3.3 STEP 7 in the TIA-Portal
SITOP UPS1600 / UPS1100
54 Operating Instructions, 05.2014, C98130-A7628-A1-4-7629
3.3.8
Firmware update
WARNING
The UPS will be reset during the firmware update. For safety reasons, the output is
switched off.
Ensure that no damage is caused to the system and that the PG/PC has a power supply
independent of the UPS during the firmware update.
The files for updating the firmware (firmware updates) are available online under
(http://support.automation.siemens.com/WW/view/de/79207181). Different firmware updates
are offered depending on the amperage of the UPS.
Note
Observe the compatibility of the firmware!
Determine the amperage of your UPS and download the appropriate firmware update. Other
firmware updates are not compatible.
Preconditions
The UPS1600 has been correctly connected, and connected with the system.
PG/PC with STEP 7 in the TIA Portal is connected with the system.
Online connection is established.
Procedure
1. Select the UPS1600 in the network view and switch to the device view.
2. In the shortcut menu of the UPS1600, select "Online & diagnostics".
The "Online gateways" open.
3. In the "Functions" folder, select the "Firmware update" group.
4. Click on the "Browse" button in the "Firmware loader" area to select the path to the
directory with the unzipped files.
5. Select the "dc_ups.upd" file. All UPS1600 are displayed in the table, for which an update
is possible with the selected firmware file.