Changing the IP address
1. Select the PROFINET interface of a PROFINET device in the Network or Device view of
the Hardware and Network editor of STEP 7 in the TIA Portal.
2. In the Inspector window navigate to "Ethernet addresses" in the "IP protocol" area.
3. Check whether the "Set IP address in the project" option is activated.
4. Enter the new IP address in the appropriate field.
Loading the configuration to the UPS1600
To commission the UPS, you must load the project data that you created offline into the
connected UPS1600. This project data results from the configuration of the hardware,
networks and connections in STEP 7 in the TIA Portal.
The complete project data is loaded for the initial loading. Only the changes are loaded for
subsequent load actions.
Preconditions
The project data is consistent.
The device name must be identical offline and online.
The UPS1600 is accessible online.
The UPS1600 is located in the Profinet IO system of an IO controller.
The PG/PC is connected to the same network to which the UPS1600 and the controller
are connected. The interface of the PG/PC must be set to TCP/IP.