3.3 STEP 7 in the TIA-Portal
SITOP UPS1600 / UPS1100
48 Operating Instructions, 05.2014, C98130-A7628-A1-4-7629
Activate interruption of the output voltage for supply system restoration
If the value is set to "Yes", the system enters a reset after a supply system restoration
during the buffering and switches the output off for a defined time (interruption time). This
option is useful, when, for example, computer networks are protected by the UPS that
can be activated by a reset when the power supply is restored.
Interruption time
The interruption time after which the power returns during buffer mode.
Signaling
Parameter
Value range
Default setting
Downtime alarm
0 … 20,000 ms
125 ms
Wait time for stable input voltage
0.005 … 65 s
0.5 s
Signaling delay for supply system failure
The time that a fault must be present before a response is made (buffering message).
Signaling delay for supply system restoration
The wait time until a stable input voltage is present.
Energy storage
The "energy storage" has two different areas that depend on the battery type being used.
First select whether you are using a UPS1100 battery module or some other energy storage
device.
Possible parameters when using a UPS1100 battery module
Parameter
Value range
Module
Drop-down menu with the UPS1100 battery modules saved by the HSP
Number of modules
0 … 6
Total capacity
0 … 42 Ah
Module
Type of UPS1100 battery module.
Number of modules
Number of the installed modules.
Total capacity
Total capacity of the installed battery modules.