3.3 STEP 7 in the TIA-Portal
SITOP UPS1600 / UPS1100
Operating Instructions, 05.2014, C98130-A7628-A1-4-7629
47
Proceed as follows
1. Select the UPS1600.
2. In the Inspector window open tab "Properties/General"
You see the possible subtabs for the parameterization.
Buffering parameters
Parameter
Value range
Default setting
Buffering allowed
Yes / No
Yes
Connection threshold
21 … 25 V
21.5 V
Buffer time
1 … 32767 s
60 s
Additional buffer time after PC shutdown
1 … 300 s
10 s
Stop buffering voltage
18 … 23 V
18.5 V
Activate interruption of the output voltage for supply system
restoration
Yes / No Yes
Interruption time
1 … 120 s
5 s
Buffering allowed
Select between buffers with the specified values or passive measurement of the power
supply by the UPS.
Connection threshold
If the connection threshold value is undershot, the UPS starts buffering. If the value of the
connection threshold is reached or undershot again later, the UPS stops buffering.
Buffer time
The time to be buffered by the UPS. The "Buffering allowed" parameter is used to specify
whether buffering should be performed.
Additional buffer time after PC shutdown
Time, to be buffered by the UPS1600 after the PC has been shut down.
Stop buffering voltage
The voltage at which battery discharge is terminated.