User manual
Engineering
3.3 STEP 7 in the TIA-Portal
SITOP UPS1600 / UPS1100
Operating Instructions, 05.2014, C98130-A7628-A1-4-7629
47
Proceed as follows
1. Select the UPS1600.
2. In the Inspector window open tab "Properties/General"
You see the possible subtabs for the parameterization.
Buffering parameters
Parameter
Value range
Default setting
Buffering allowed
Yes / No
Yes
Connection threshold
21 … 25 V
21.5 V
Buffer time
1 … 32767 s
60 s
Additional buffer time after PC shutdown
1 … 300 s
10 s
Stop buffering voltage
18 … 23 V
18.5 V
Activate interruption of the output voltage for supply system
restoration
Yes / No Yes
Interruption time
1 … 120 s
5 s
●
Buffering allowed
Select between buffers with the specified values or passive measurement of the power
supply by the UPS.
●
Connection threshold
If the connection threshold value is undershot, the UPS starts buffering. If the value of the
connection threshold is reached or undershot again later, the UPS stops buffering.
●
Buffer time
The time to be buffered by the UPS. The "Buffering allowed" parameter is used to specify
whether buffering should be performed.
●
Additional buffer time after PC shutdown
Time, to be buffered by the UPS1600 after the PC has been shut down.
●
Stop buffering voltage
The voltage at which battery discharge is terminated.