User manual
Engineering
3.3 STEP 7 in the TIA-Portal
SITOP UPS1600 / UPS1100
44 Operating Instructions, 05.2014, C98130-A7628-A1-4-7629
6. Select the PROFINET-interface.
7. Under "Ethernet addresses" in the inspector window enter the IP address of the
UPS1600, which was already assigned in the TIA-Portal .
You have assigned the UPS1600 a controller.
3.3.3
Assigning the UPS1600 battery modules
The basic functions of the uninterruptible power supply are available with all of the battery
modules that are compatible with the UPS1600.
Additional functions are available with the UPS1100 battery module:
● Automatic detection of the battery module rated values
● Automatic management of up to 6 battery modules
● Temperature-controlled charging
● Battery fast test
● Diagnostics using SITOP UPS Manager and the web server
Using an example, in the following steps it is shown how a UPS1100 battery module is
assigned to the UPS1600.
Note
Only UPS1100 battery modules of the same type can be inserted into the slots of a
UPS1600.
The number of UPS1100 battery modules that can be
configured is limited to 6.
Preconditions
● STEP 7 in the TIA-Portal has been opened and a project has been created.
● A UPS1600 has been integrated in the project.
Procedure
1. In the device view, select the UPS1600.
2. In the Hardware catalog , navigate to the UPS1100 battery module under Power
supplies\SITOP UPS\UPS1600.
3. Select the required UPS1100 battery module in the hardware catalog.