User manual

Engineering
3.2 Alarm list
SITOP UPS1600 / UPS1100
40 Operating Instructions, 05.2014, C98130-A7628-A1-4-7629
Error
Type
Extended
Error Type
Maintenance
Alarm Text
Help Text
257 17 F DC UPS parameters corrupt DC UPS parameters corrupt - try to update the
software
257 18 F Device overtemperature Output and battery charging is switched off to
prevent damage to the device.
257
19
MR
Reserve
257 20 MR Low voltage mode Input voltage of DC UPS is too low. DC UPS is not
operational.
257
21
MR
Buffering
Device is in buffer mode
257 22 MD Communication with device
failed
PROFINET connection available - DC UPS is
defective
257
23
MR
Device powered up
Device powered up
257
24
F
Wrong battery polarity
Wrong battery polarity - check battery connections.
257
25
MD
Reserve
257 26 MR Insufficient charge level The battery charge level is too low to guarantee the
configured buffer time.
257
27
MR
Deep discharge battery
Battery is deep discharged - no buffering possible
258
-
F
Battery diagnostics
Battery diagnostics
258 1 F Battery defective (battery
index: {1:d})
Battery defective - check the fuse and the battery
voltages
258 2 F Deep discharge battery, no
charging possible (battery
index: {1:d})
Battery is deep discharged - replace battery
258 3 MD Battery temperature high
(battery index: {1:d})
Battery temperature too high - battery life will be
shortened
258 4 MD Battery temperature low
(battery index: {1:d})
Battery temperature too low - reduced output
current
258 5 F Communication with battery
fault (battery index: {1:d})
Communication with formerly known battery is no
longer possible - check communication
258 6 MR New battery detected
(battery index: {1:d})
A new battery was connected. The battery will be
included in the calculation of the total capacity and
the charge parameters.
258 7 F Wrong battery configuration
(battery index: {1:d})
Different battery types connected. Only batteries of
the same type can be operated together.
258 8 MD Battery parameters corrupt
(battery index: {1:d})
Battery defective - replace battery
258 9 MR Battery replacement started
(battery index: {1:d})
Battery replacement started by user
258 10 MR Battery replacement finished
(battery index: {1:d})
Battery replacement finished - counters have been
reset
258 11 MD Battery replacement
canceled (battery index:
{1:d})
Battery replacement canceled - battery parameters
are not reset