Description, device design, dimension drawing
2.4 Operating displays and signaling
SITOP UPS1600 / UPS1100
28 Operating Instructions, 05.2014, C98130-A7628-A1-4-7629
LED 4 (accumulator / bat. fault)
Signaling
6EP4134-3AB00-...
6EP4136-3AB00-...
Off Battery OK or uncoded battery modules connected or backup time rotary coding switch at
position MAX
Flashing yellow
(0.5/0.5)
Battery outside the permitted temperature range
Red
Battery defective
Yellow
Selected backup time cannot be attained
LED 5 and LED 6 (PROFINET LEDs)
Signaling
6EP4134-3AB00-2AY0
6EP4136-3AB00-2AY0
LED 5 (SF)
LED 6 (RUN)
Off
Off
No connection to a PROFINET IO controller
Off
Flashing green
(0.5/0.5)
Configuration by the PROFINET IO controller
Off
Green
Application started successfully, module OK
Red
Green
Application started successfully, module not OK
Flashing red (0,1/0,1)
Green
Application in progress, diagnosis can be called
Flashing red (0.5/0.5)
Flashing green
(0.5/0.5)
Self-test in progress (flashing alternately every 3 seconds)
Flashing red (0.5/0.5)
Off DCP requires device identification (LED flashes for
3 seconds)
Flashing red (0.5/0.5)
Flashing green
(0.5/0.5)
Updating the firmware
LED 5 and 6 are active only for ... -2AY0
LED 7 (Ethernet LED / P2)
Signaling
6EP4134-3AB00-2AY0
6EP4136-3AB00-2AY0
Off
Device not connected with controller
Green
Device connected with controller, no activity
Green/orange alternately
Device connected with controller, send/receive data (RX/TX)
LED 7 is active only for ... -2AY0