User manual

Description, device design, dimension drawing
2.4 Operating displays and signaling
SITOP UPS1600 / UPS1100
Operating Instructions, 05.2014, C98130-A7628-A1-4-7629
27
LED 1 (OK/Bat)
Signaling
6EP4134-3AB00-...
6EP4136-3AB00-...
Off
DC-UPS off
Red
DC-UPS defect (severe hardware fault)
Flashing red (0.5/0.5)
Firmware update
Flashing red (1/1)
Software corrupted
Flashing yellow
(0.5/0.5)
Critical temperature reached, overtemperature or overvoltage at the input
Flashing yellow (0.5/3)
Buffer mode, output off
Yellow
Buffer mode
Flashing green (0.5/3)
DC-UPS OK, output off
Green
DC-UPS OK
LED 2 (Bat. > 85%)
Signaling
6EP4134-3AB00-...
6EP4136-3AB00-...
Flashing green
(0.5/0.5)
Updating the firmware
Off
Battery charge state < 85%
Green
Battery charge state > 85%
LED 3 (alarm)
Signaling
6EP4134-3AB00-...
6EP4136-3AB00-...
Red Output off for 45 seconds because of overcurrent, overtemperature or buffer operation not
possible
Off
Buffer operation possible