Description, device design, dimension drawing
2.3 Switches and buttons
SITOP UPS1600 / UPS1100
24 Operating Instructions, 05.2014, C98130-A7628-A1-4-7629
Start from the battery (pin 14)
The start from the battery is initiated by closing the contact pin 14 to ground (pin 10). This
jumper must not provide a permanent connection, but must be controlled using a button. The
input is designed so that a single lamp with a permissible supply voltage of between 12 and
30 V and 8 to 15 mA can be switched in series to the switching contact. If while pressing the
button, the UPS1600 enters buffer mode, the set buffer time will be started. For example, if
5 minutes is set, the UPS1600 sets itself off after 5 minutes. If the input voltage returns
during the buffer time, the UPS1600 switches to normal operation.
If the input voltage is available, the DC UPS starts in the normal operation.
If the UPS1600 is switched-off remotely via the interface (also possible when input voltage is
available), start from the battery can be used to restart the UPS1600.
Charge current setting (pin 10 / 11 / 12)
For uncoded batteries, the size of the charge current can be changed by placing jumpers
between the terminals X2.10 (ground) and X2.11 or X2.12.
Table 2- 4 Charge current
UPS1600 10 A
UPS1600 20 A
Terminal X2.11
Terminal X2.12
0.3 A
0.8 A
open
open
0.8 A
1.75 A
open
connected with X2.10
Max.
Max.
connected with X2.10
open