Description, device design, dimension drawing
2.3 Switches and buttons
SITOP UPS1600 / UPS1100
20 Operating Instructions, 05.2014, C98130-A7628-A1-4-7629
2.3
Switches and buttons
2.3.1
UPS1600
2.3.1.1
Rotary coding switch, switch-in threshold
The switch-in threshold can be set using the rotary coding switch on the device front
between 21.0 V and 25-0 V (21 - 21.5 - 22 - 22.5 - 23 - 24 - 25 volt). The delivery state is
22.5 V
For devices with an interface (…-1AY0, …-2AY0), the coding switch has an additional
position (REN, see the following figure). If this is selected, the software settings (for the
switch-in threshold and the backup time) apply rather than the hardware settings. In the
switch position REN, the connection X2.13 (INTERRUPT - reset after buffer operation) of the
signal terminal (see Section Signal terminal (Page 16)) has no effect.
Figure 2-10 Rotary coding switch, switch-in threshold
Note
It is only permissible to actuate the rotary coding switch using an insulated screwdriver.
For notes on actuating the rotary coding switch (screwdriver, torque), see Figure 2-3
UPS1600 terminal data (Page 15).