Ambient conditions
SITOP UPS1600 / UPS1100
124 Operating Instructions, 05.2014, C98130-A7628-A1-4-7629
6EP4134-3AB00-... (10 A)
6EP4136-3AB00-... (20 A)
6EP4131-0GB00-0AY0
(1.2 Ah)
6EP4133-0GB00-0AY0
(3.2 Ah)
6EP4134-0GB00-0AY0
(7 Ah)
Damaging gases Tested according to:
• EN 60068-2-42 sulfur dioxide
• EN 60068-2-43 hydrogen sulfide
Atmospheric pressure Operation:
• 1080 ... 795 hPa (-1000 ... +2000 m)
• For operation at altitudes of 2000 m up to 6000 m above sea level:
output must be derated by -7.5% / 1000 m or
the ambient temperature must be reduced by 5 K / 1000 m
see Figure 5-3 Altitude derating (Page 106)
• Overvoltage category:
III up to 2000 m (EN 50178)
II from 2000 m up to 6000 m (EN 50178)
Storage:
• 1080 ... 660 hPa (-1000 ... +3500 m)