User manual
SITOP UPS1600 / UPS1100
Operating Instructions, 05.2014, C98130-A7628-A1-4-7629
123
Ambient conditions
9
6EP4134-3AB00-... (10 A)
6EP4136-3AB00-... (20 A)
6EP4131-0GB00-0AY0
(1.2 Ah)
6EP4133-0GB00-0AY0
(3.2 Ah)
6EP4134-0GB00-0AY0
(7 Ah)
Ambient temperature -25 ... +70° C with natural
convection
-25 ... +60° C with natural
convection
15 A (derating) at
60° ... 70° C
0 ... +40° C with natural
convection
Tested according to:
• EN 60068-2-1 cold
• EN 60068-2-2 dry heat
• EN 60068-2-78 humid heat, constant
• EN 60068-2-14 temperature change
Note: The service life of the UPS1100 battery modules (reduce to 50% of the original
capacity) depends on the battery temperature, for approximately +20° C: 4 years, +30° C:
2 years, +40° C: 1 year
Transport and storage
temperature
-40 ... +85° C
-20 ... +50° C
Tests (packed for shipping) according to:
• EN 60068-2-1 cold
• EN 60068-2-2 dry heat
• EN 60068-2-30 humid heat, cyclic
Humidity class
Climatic class 3K3 according to EN 60721, without condensation
Degree of pollution
2
Mechanical stressing during
operation
Tested according to:
• EN 60068-2-6 Vibration, test Fc:
3.5 mm deflection in the range 5 – 9 Hz
1 g acceleration in the range 9 – 150 Hz
• EN 60068-2-27 shock, test Ea:
acceleration 150 m/s
2
, test duration 11 ms