User manual
Technical data
7.2 Output
SITOP UPS1600 / UPS1100
114 Operating Instructions, 05.2014, C98130-A7628-A1-4-7629
7.2
Output
7.2.1
UPS1600
6EP4134-3AB00-... (10 A)
6EP4136-3AB00-... (20 A)
Output voltage with normal operation
Input voltage Ui minus approximately 0.2 V
Output voltage for buffer mode 27 VDC (no-load); 24 V (50% battery rated current);
22 V (100% battery rated current); 18.5 V (exhaustive discharge protection)
Power-up characteristics Startup delay < 1 s
Typical voltage increase: < 60 ms
Output +Bat/-Bat for normal operation
• Remark
I-U charging characteristic (initially fast charge current, then charge retention).
Maximum 0.3 CA for a connected battery module; maximum 0.4 for several
parallel connected battery modules.
End-of-charge voltage
Automatic temperature-controlled setting with SITOP UPS1100 battery modules.
Output current – rated value
• Power boost for 30 ms
• Extra power for 5 s/min
10 A
30 A
15 A
20 A
60 A
30 A
Charge current Max. 3 A
Automatic setting for UPS1100;
otherwise 0.3 A, 0.8 A or 3 A can be
selected (by software or jumper (see
Table 2-4 Charge current (Page 24)))
Max. 4 A
Automatic setting for UPS1100;
otherwise 0.8 A, 1.75 A, 4 A can be
selected (by software or jumper (see
Table 2-4 Charge current (Page 24)))
7.2.2
UPS1100
6EP4131-0GB00-0AY0
(1.2 Ah)
6EP4133-0GB00-0AY0
(3.2 Ah)
6EP4134-0GB00-0AY0
(7 Ah)
Output voltage rated value 24 VDC, 22...27.0 VDC (no-load)
Output current rated value 10 A 20 A 40 A
Battery fuse (plug-in) 15 A / 32 V 25 A / 32 V 2x25 A / 32 V