User manual

SITOP UPS1600 / UPS1100
Operating Instructions, 05.2014, C98130-A7628-A1-4-7629
113
Technical data
7
Note
Technical data is applicable for a rated input voltage, rated load and +25°
C ambient
temperature (if nothing else is specified).
7.1
Input
7.1.1
UPS1600
6EP4134-3AB00-... (10 A)
6EP4136-3AB00-... (20 A)
Input voltage Ui rated / range
24 VDC (21 ... 29 V)
Connection threshold for buffering
Remark
22.5 VDC ± 3% (factory setting),
setting range: 21 VDC , 21.5 VDC , 22 VDC, 22.5 VDC, 23 VDC, 24 VDC,
25 VDC or via software.
The connection threshold must be at least 0.5 V lower than the input voltage.
After reaching the minimum input voltage at the DC UPS module, the module
cannot buffer for a maximum of 1.5 seconds.
Input current Ii rated Approximately 14 A for the max. charge
current (3 A)
Approximately 25 A for the max. charge
current (4 A)
Reverse polarity protection
Yes
7.1.2
UPS1100
Charging current: Maximum 0.3 CA for a connected battery module; maximum 0.4 CA is
permitted for several parallel connected battery modules.