6.6 UPS1100 connections
SITOP UPS1600 / UPS1100
110 Operating Instructions, 05.2014, C98130-A7628-A1-4-7629
6.6
UPS1100 connections
Connections 1.2/3.2
Ah
Connections 7 Ah
Connection X1 ①
The connections "X1+" and "X1-" are used to transfer power between the UPS1600 with
UPS1100. Ensure that the cables are dimensioned corresponding to the fuses in the
UPS1100 and the impedances between UPS1600 and UPS1100 are identical. Only connect
charged batteries with one another.
Connection X2 ②
The "X2-1" and "X2-2" connections are used to exchange data between the UPS1600 and
UPS1100. (see Figure 6-1 Wiring (Page 107))
When several battery modules are used, note the following:
● As many as six battery modules of the same type can be connected together in parallel.
● If different battery modules are connected in parallel, relay 2 flashes (battery defective).
No calculations with regard to charge and remaining buffer time are performed. The
battery modules are not charged, but buffering is possible.
● If more than six battery modules are connected in parallel, relay 2 flashes (battery
defective). No calculations with regard to charge and remaining buffer time are
performed. Charging and buffering, however, is possible.