User manual

Installation
6.3 Connecting the BAT UPS1600
SITOP UPS1600 / UPS1100
Operating Instructions, 05.2014, C98130-A7628-A1-4-7629
109
6.3
Connecting the BAT UPS1600
Figure 6-4 BAT connection
The "BAT+" and "BAT-" connections (see Figure 6-4 BAT connection (Page 109)) are
used to connect the UPS1600 with one or more UPS1100 battery modules. Ensure that the
cables are dimensioned correctly for the maximum output current rms value of the UPS1600.
For wiring, see Figure 6-1 Wiring (Page 107).
The deployed cables must be suitable for temperatures of at least 90° C. (only for
applications for UL508)
Maximum cable length 3 m
6.4
USB interface
Maximum USB cable length 5 m
6.5
PROFINET/Ethernet connection
Maximum length of the PROFINET/Ethernet cable 100 m (90 m BASIC- Link plus 2 x 5 m
CHANNEL- Link)