Mounting position, mounting clearances
5.2 UPS1100
SITOP UPS1600 / UPS1100
Operating Instructions, 05.2014, C98130-A7628-A1-4-7629
105
5.2
UPS1100
5.2.1
Standard mounting position
The device is suitable for the direct wall mounting. The 6EP4131-0GB00-0AY0 (1.2 Ah) and
6EP4133-0GB00-0AY0 (3.2 Ah) devices can be snapped onto a standard mounting rail
EN 60715 35×15, and the 6EP4131-0GB00-0AY0 (1.2 Ah) device can also be snapped onto
a standard mounting rail EN 60715 35×7.5. It should also be mounted at the coolest point in
the control cabinet (e.g. in the lower part of the control cabinet). The device must be
mounted vertically in such a way that the input terminals and the output terminals are at the
bottom to ensure correct cooling.
No clearance is required at the side.
5.2.2
Other mounting positions
Not released.