User manual
Mounting/removal
4.2 UPS1100
SITOP UPS1600 / UPS1100
100 Operating Instructions, 05.2014, C98130-A7628-A1-4-7629
4.2
UPS1100
WARNING
Mounting the device in a housing or a control cabinet
The SITOP UPS1100 battery modules are built-in units. They must be mounted in a
housing or control cabinet where only qualified personnel have access.
The device is suitable for direct wall mounting.
The 6EP4131-0GB00-0AY0 (1.2 Ah) and 6EP4133-0GB00-0AY0 (3.2 Ah) devices can be
snapped onto a standard mounting rail EN 60715 35×15, and the 6EP4131-0GB00-0AY0
(1.2 Ah) device can also be snapped onto a standard mounting rail EN 60715 35×7.5.
The lower part of the control cabinet or the coolest location in the control cabinet should be
chosen as mounting location.
Mounting
For the drilled holes for the wall mounting, refer to the "Dimensions and weight" UPS1100
(Page 35) section.
To mount the device on a standard mounting rail, place it with the standard mounting rail
guide at the upper edge of the standard mounting rail and snap it in downwards. If this is too
difficult, push the device downwards while pressing on the rail as described for "Removal".
Note
The fuses should be inserted in the fuse holder only when commissioning the device
(charged batteries).