Datasheet
Safety
Protection class Class III
CE mark Yes
UL/cUL (CSA) approval cURus-Recognized (UL 1778, CSA C22.2 No. 107.1), File
E219627
Explosion protection IECEx Ex nA nC IIC T4 Gc; cCSAus (CSA C22.2 No. 213-M1987,
ANSI/ISA-12.12.01-2013) Class I, Div. 2, Group ABCD, T4
Marine approval DNV GL, ABS
Degree of protection (EN 60529) IP20
Operating data note
Operating data note For storage, mounting and operation of lead-acid batteries, the
relevant DIN/VDE regulations or country-specific regulations (e.g.
VDE 0510 Part 2/EN 50272-2) must be observed. You must
ensure that the battery site is sufficiently ventilated. Possible
sources of ignition must be at least 50 cm away.
Ambient temperature
● during operation
-15...+50°C
● during transport
-20...+50°C
● during storage
-20...+50°C
Relative temporary capacity loss at 20 °C in a month
typical
3%
Service life
Service life of energy storage
● typical Note
capacity falls to 50 % of original capacity
● at 20 °C typical
4y
● at 30 °C typical
2y
● at 40 °C typical
1y
● at 50 °C typical
0.5y
Ambient temperature during storage Note Along with the storage and operating temperature, other factors
such as the duration of the storage period and the charge status
during storage have a decisive influence on the possible useful
life. Batteries should therefore be stored as briefly as possible,
always fully charged, and within the temperature range 0 to +20
°C.
Mechanics
Connection technology screw-type terminals
Connection for power supply unit 1 screw terminal each for 0.2 ... 6 mm² for + BATT and - BATT
Type of electrical connection for control circuit and
status message
1 screw terminal each for 0.14 ... 4 mm²
Product component belonging to Accessories pack with solid-state circuitry fuse 15 A
Width of the enclosure 89mm
Height of the enclosure 130mm
Depth of the enclosure 107mm
6EP4131-0GB00-0AY0 Subject to change without notice
Page 2/
3
04/05/2018 © Copyright Siemens