Datasheet
Explosion protection IECEx Ex nA nC IIC T4 Gc; ATEX (EX) II 3G Ex nA nC IIC T4 Gc;
cCSAus (CSA C22.2 No. 213, ANSI/ISA-12.12.01) Class I, Div. 2,
Group ABCD, T4
FM approval -
CB approval Yes
Marine approval ABS, DNV GL
Degree of protection (EN 60529) IP20
EMC
Emitted interference EN 55022 Class B
Supply harmonics limitation EN 61000-3-2
Noise immunity EN 61000-6-2
Operating data
Ambient temperature
● during operation
-25...+60°C
— Note
with natural convection
● during transport
-40...+85°C
● during storage
-40...+85°C
Humidity class according to EN 60721 Climate class 3K3; in addition 95% maximum relative humidity,
but without condensation
Mechanics
Connection technology Plug-in terminals with screwed connection
Connections
● Supply input
L1, L2, L3, PE: Plug-in terminal with 1 screwed connection each
for 0.2 ... 4 mm² single-wire / fine stranded
● Output
1, 2, 3, 4: Two plug-in terminals (1, 2 and 3, 4) with 2 screwed
connections each for 0.2 ... 2.5 mm²; 0 V: Plug-in terminal with 3
screwed connections for 0.2 ... 10 mm²
● Auxiliary
RST (Reset): Plug-in terminal (together with alarm signal) with 1
screwed connection for 0.2 ... 1.5 mm²
Connections signaling contact 11, 12, 14 (alarm signal): Plug-in terminal (together with Reset)
with 1 screwed connection each for 0.2 ... 1.5 mm²
Product function
● removable terminal at input
Yes
● removable terminal at output
Yes
Design of the interface for communication PROFINET/Ethernet: two RJ45 sockets (2-port switch)
Suitability for interaction modular system Yes
Width of the enclosure 125mm
Height of the enclosure 125mm
Depth of the enclosure 150mm
Required spacing
● top
50mm
● bottom
50mm
● left
0mm
6EP3437-8MB00-2CY0 Subject to change without notice
Page 4/
5
07/30/2018 © Copyright Siemens