Datasheet
Protection in the mains power input (IEC 898) Required: 3-pole connected miniature circuit breaker 10 ... 16 A
characteristic C or circuit breaker 3RV2011-1DA10 (setting 3 A) or
3RV2711-1DD10 (UL 489)
Output
Output Controlled, isolated DC voltage
Number of outputs 4
Rated voltage Vout DC 24V
Output voltage
● at output 1 at DC Rated value
24V
● at output 2 at DC Rated value
24V
● at output 3 at DC Rated value
24V
● at output 4 at DC Rated value
24V
Total tolerance, static ± 3%
Static mains compensation, approx. 0.2%
Static load balancing, approx. 0.1%
Residual ripple peak-peak, max. 100mV
Spikes peak-peak, max. (bandwidth: 20 MHz) 200mV
Adjustment range 4...28V
Product function Output voltage adjustable Yes
Output voltage setting via potentiometer; Derating > 24 V: 4%/V; max. 240 W per output,
max. 960 W overall system
Status display 3-color LED for operating state device; LED for operating mode
manual/remote; 4 LEDs for communication PROFINET; 3-color
LED per output for operating state output; LED green for parallel
operation Output 1 and 2 / 3 and 4
Signaling Relay contact (changeover contact, contact current capacity DC
60 V/0.3 A) for "Operating state OK"
On/off behavior No overshoot of Vout (soft start)
Startup delay, max. 1s; Without on-delay of the outputs
connection of outputs operating Simultaneous connecting-in of all outputs after device booting or
delay time of 25ms, 100ms or "load-optimized" for sequential
cutting-in of the outputs via DIP switches can be set
Voltage increase time of the output voltage maximum 500ms
Rated current value Iout rated 40A
Output current
● per output
10A
● at output 1 Rated value
10A
● at output 2 Rated value
10A
● at output 3 Rated value
10A
● at output 4 Rated value
10A
Current range 0...40A
● Note
+50 ... +60 °C: Derating 2.5%/K; no derating in connection with
expansion module CNX8600 and total load of the outputs at the
basic device max. 480 W
6EP3437-8MB00-2CY0 Subject to change without notice
Page 2/
5
07/30/2018 © Copyright Siemens