Datasheet

Dynamic load smoothing (Iout: 50/100/50 %), Uout ±
typ.
5%
Setting time maximum 0.2ms
Protection and monitoring
Output overvoltage protection ≤ 60 V according to EN 60950-1
Current limitation 2...10A
Current limitation Can be set with potentiometer or analog control voltage signal 0.5
... 2.5 V
Property of the output Short-circuit proof Yes
Short-circuit protection Electronic current limiting (2 ... 10 A) in the range 3 ... 12 V or
power limiting (120 W) in the range 12 ... 52 V
Enduring short circuit current RMS value
● maximum
12A
Safety
Primary/secondary isolation Yes
Galvanic isolation Safety extra low output voltage Vout according to EN 60950-1
Protection class Class I
Leakage current
● maximum
3.5mA
Degree of protection (EN 60529) IP20
Approvals
CE mark Yes
UL/cUL (CSA) approval cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259
Explosion protection -
FM approval -
CB approval Yes
Marine approval -
EMC
Emitted interference EN 55022 Class B
Supply harmonics limitation EN 61000-3-2
Noise immunity EN 61000-6-2
environmental conditions
Ambient temperature
● during operation
-25...+70°C
— Note
Derating > 60°C: 2%/°K
● during transport
-40...+85°C
● during storage
-40...+85°C
Humidity class according to EN 60721 Climate class 3K3, no condensation
Mechanics
Connection technology screw-type terminals
Connections
6EP3343-0SA00-0AY0 Subject to change without notice
Page 3/
4
06/20/2019 © Copyright Siemens