Rated voltage Vout DC 24V
Total tolerance, static ± 2%
Static mains compensation, approx. 0.1%
Static load balancing, approx. 0.6%
Residual ripple peak-peak, max. 150mV
Residual ripple peak-peak, typ. 20mV
Spikes peak-peak, max. (bandwidth: 20 MHz) 250mV
Spikes peak-peak, typ. (bandwidth: 20 MHz) 40mV
Adjustment range 24...28V
Product function Output voltage adjustable Yes
Output voltage setting via potentiometer
Status display Green LED for 24 V OK
On/off behavior No overshoot of Vout (soft start)
Startup delay, max. 0.5s
Voltage rise, typ. 10ms
Voltage increase time of the output voltage maximum 20ms
Rated current value Iout rated 4A
Current range 0...4A
● Note
+60 ... +70 °C: Derating 2%/K
Supplied active power typical 108W
Parallel switching for enhanced performance Yes
Numbers of parallel switchable units for enhanced
performance
2
Efficiency
Efficiency at Vout rated, Iout rated, approx. 89%
Power loss at Vout rated, Iout rated, approx. 12W
Power loss [W] during no-load operation maximum 1.5W
Closed-loop control
Dynamic mains compensation (Vin rated ±15 %),
max.
0.3%
Dynamic load smoothing (Iout: 50/100/50 %), Uout ±
typ.
2%
Load step setting time 50 to 100%, typ. 1ms
Load step setting time 100 to 50%, typ. 1ms
Protection and monitoring
Output overvoltage protection Ua < 35 V
Current limitation, typ. 4.5A
Property of the output Short-circuit proof Yes
Short-circuit protection Electronic shutdown, automatic restart
Overload/short-circuit indicator Yellow LED overload
Safety
Primary/secondary isolation Yes
6EP3133-0TA10-0AY0 Subject to change without notice
Page 2/
4
08/07/2019 © Copyright Siemens