Datasheet

Output Controlled, isolated DC voltage
Rated voltage Vout DC 12V
Total tolerance, static ± 2%
Static mains compensation, approx. 0.2%
Static load balancing, approx. 1%
Residual ripple peak-peak, max. 150mV
Residual ripple peak-peak, typ. 30mV
Spikes peak-peak, max. (bandwidth: 20 MHz) 250mV
Spikes peak-peak, typ. (bandwidth: 20 MHz) 50mV
Adjustment range 12...15.5V
Product function Output voltage adjustable Yes
Output voltage setting via potentiometer
Status display Green LED for 12 V OK
Signaling Relay contact (NO contact, contact rating 30 V AC/0.5 A; 60 V
DC/0.3 A; 30 V DC/1 A) for 12 V O.K.
On/off behavior No overshoot of Vout (soft start)
Startup delay, max. 0.5s
Voltage rise, typ. 5ms
Voltage increase time of the output voltage maximum 10ms
Rated current value Iout rated 15A
Current range 0...15A
● Note
+60 ... +70 °C: Derating 2%/K
Supplied active power typical 200W
Parallel switching for enhanced performance Yes
Numbers of parallel switchable units for enhanced
performance
2
Efficiency
Efficiency at Vout rated, Iout rated, approx. 91%
Power loss at Vout rated, Iout rated, approx. 21W
Power loss [W] during no-load operation maximum 0.5W
Closed-loop control
Dynamic mains compensation (Vin rated ±15 %),
max.
0.3%
Dynamic load smoothing (Iout: 50/100/50 %), Uout ±
typ.
4%
Load step setting time 50 to 100%, typ. 2ms
Load step setting time 100 to 50%, typ. 2ms
Protection and monitoring
Output overvoltage protection Ua < 22 V
Current limitation, typ. 16A
Property of the output Short-circuit proof Yes
Short-circuit protection Electronic shutdown, automatic restart
Overload/short-circuit indicator Yellow LED overload
6EP3124-0TA00-0AY0 Subject to change without notice
Page 2/
4
07/16/2019 © Copyright Siemens