Datasheet
Operating data
• note For storage, mounting and operation of lead-acid batteries, the
relevant DIN/VDE regulations or country-specific regulations (e.g.
VDE 0510 Part 2/EN 50272-2) must be observed. You must ensure
that the battery site is sufficiently ventilated. Possible sou
Ambient temparature
• in operation -15 … +50 °C
• on transport -20 … +50 °C
• in storage -20 … +50 °C
Relative, temporary capacity loss / at 20 °C / in a month / typical 3 %
Service life
Service life of lead-acid battery
• typical / note capacity falls to 50 % of original capacity
• at 20 °C / typical 4 a
• at 30 °C / typical 2 a
• at 40 °C / typical 1 a
• at 50 °C / typical 0.5 a
Mechanics
Connection technology spring-loaded terminals
Design of the electrical connection 1 screw terminal each for 0.08 ... 2.5 mm² for + BATT and - BATT
Product component / belonging to Accessories pack with solid-state circuitry fuse 15 A
Width / of the housing 190 mm
Height / of the housing 151 mm
Depth / of the housing 82 mm
Installation width 210 mm
Mounting height 171 mm
Net weight 3.2 kg
Installation snaps onto DIN rail EN 60715 35x7.5/15 or keyhole mounting for
hooking in to M4 screws
Number of cells 12
Other information Specifications at rated input voltage and ambient temperature +25
°C (unless otherwise specified)
6EP1935-6MD11
Page 2/ 10/01/2012
subject to modifications
© Copyright Siemens AG 2012
3