Datasheet

Short-circuit protection Electronic shutdown, automatic restart
Enduring short circuit current RMS value
● maximum
0.9A
Overload/short-circuit indicator -
Safety
Primary/secondary isolation Yes
Galvanic isolation Safety extra-low output voltage Uout acc. to EN 60950-1 and EN
50178
Protection class Class I
Leakage current
● maximum
3.5mA
CE mark Yes
UL/cUL (CSA) approval cULus-Listed (UL 508, CSA C22.2 No. 142), File E143289,
cURus-Recognized (UL 60950, CSA C22.2 No. 60950), File
E151273
Explosion protection -
FM approval -
CB approval No
Marine approval -
Degree of protection (EN 60529) IP20
EMC
Emitted interference EN 55022 Class B
Supply harmonics limitation not applicable
Noise immunity EN 61000-6-2
Operating data
Ambient temperature
● during operation
-25...+70°C
— Note
with natural convection
● during transport
-40...+70°C
● during storage
-40...+70°C
Humidity class according to EN 60721 Climate class 3K3, no condensation
Mechanics
Connection technology screw-type terminals
Connections
● Supply input
L+1, M1, PE: 1 screw terminal each for 0.5 ... 2.5 mm² single-
core/finely stranded
● Output
+: 1 screw terminal for 0.5 ... 2.5 mm²; -: 2 screw terminals for 0.5
... 2.5 mm²
● Auxiliary
-
Width of the enclosure 22.5mm
Height of the enclosure 80mm
Depth of the enclosure 91mm
6EP1731-2BA00 Subject to change without notice
Page 3/
4
11/22/2016 © Copyright Siemens AG