Static mains compensation, approx. 3%
Static load balancing, approx. 3%
Residual ripple peak-peak, max. 150mV
Residual ripple peak-peak, typ. 35mV
Spikes peak-peak, max. (bandwidth: 20 MHz) 240mV
Spikes peak-peak, typ. (bandwidth: 20 MHz) 70mV
Adjustment range 24...29V
Product function Output voltage adjustable Yes
Output voltage setting via potentiometer; max. 120 W
Status display Green LED for 24 V OK
Signaling Relay contact (NO contact, rating 60 V DC/ 0.3 A) for "24 V OK"
On/off behavior Overshoot of Vout approx. 3 %
Startup delay, max. 0.5s
Voltage rise, typ. 10ms
Voltage increase time of the output voltage maximum 100ms
Rated current value Iout rated 5A
Current range 0...5A
Active power supplied typical 120W
Short-term overload current on short-circuiting during
the start-up typical
33A
Duration of overloading capability for excess current
on short-circuiting during the start-up
140ms
Short-term overload current at short-circuit during
operation typical
28A
Duration of overloading capability for excess current
at short-circuit during operation
135ms
Parallel switching for enhanced performance No
Efficiency
Efficiency at Vout rated, Iout rated, approx. 90%
Power loss at Vout rated, Iout rated, approx. 13W
Closed-loop control
Dynamic mains compensation (Vin rated ±15 %),
max.
3%
Dynamic load smoothing (Iout: 50/100/50 %), Uout ±
typ.
5%
Load step setting time 50 to 100%, typ. 1ms
Load step setting time 100 to 50%, typ. 1ms
Dynamic load smoothing (Iout: 10/90/10 %), Uout ±
typ.
1%
Load step setting time 10 to 90%, typ. 1ms
Load step setting time 90 to 10%, typ. 1ms
Setting time maximum 30ms
Protection and monitoring
6EP1433-0AA00 Changes preserved
Page 2/