Datasheet
Static mains compensation, approx. 3%
Static load balancing, approx. 3%
Residual ripple peak-peak, max. 150mV
Residual ripple peak-peak, typ. 35mV
Spikes peak-peak, max. (bandwidth: 20 MHz) 240mV
Spikes peak-peak, typ. (bandwidth: 20 MHz) 70mV
Adjustment range 24...29V
Product function Output voltage adjustable Yes
Output voltage setting via potentiometer; max. 120 W
Status display Green LED for 24 V OK
Signaling Relay contact (NO contact, rating 60 V DC/ 0.3 A) for "24 V OK"
On/off behavior Overshoot of Vout approx. 3 %
Startup delay, max. 0.5s
Voltage rise, typ. 10ms
Voltage increase time of the output voltage maximum 100ms
Rated current value Iout rated 5A
Current range 0...5A
Active power supplied typical 120W
Short-term overload current on short-circuiting during
the start-up typical
33A
Duration of overloading capability for excess current
on short-circuiting during the start-up
140ms
Short-term overload current at short-circuit during
operation typical
28A
Duration of overloading capability for excess current
at short-circuit during operation
135ms
Parallel switching for enhanced performance No
Efficiency
Efficiency at Vout rated, Iout rated, approx. 90%
Power loss at Vout rated, Iout rated, approx. 13W
Closed-loop control
Dynamic mains compensation (Vin rated ±15 %),
max.
3%
Dynamic load smoothing (Iout: 50/100/50 %), Uout ±
typ.
5%
Load step setting time 50 to 100%, typ. 1ms
Load step setting time 100 to 50%, typ. 1ms
Dynamic load smoothing (Iout: 10/90/10 %), Uout ±
typ.
1%
Load step setting time 10 to 90%, typ. 1ms
Load step setting time 90 to 10%, typ. 1ms
Setting time maximum 30ms
Protection and monitoring
6EP1433-0AA00 Changes preserved
Page 2/
4
19.03.2015 © Copyright Siemens AG