Datasheet

Output voltage 2 x 15 V DC
Output voltage at output 1 for DC Rated value 15V
Output voltage at output 2 for DC Rated value 15V
Total tolerance, static ± 2%
Static mains compensation, approx. 0.2%
Static load balancing, approx. 0.2%
Residual ripple peak-peak, max. 50mV
Residual ripple peak-peak, typ. 20mV
Spikes peak-peak, max. (bandwidth: 20 MHz) 150mV
Adjustment range 14.5...17V
Product function Output voltage adjustable Yes
Output voltage setting via potentiometer
Status display Green LED grün for Vout >10 V (summation display)
Signaling -
On/off behavior Overshoot of Vout < 3 %
Startup delay, max. 1s
Rated current value Iout rated 3.5A
Output current at output 1 Rated value 3.5A
Output current at output 2 Rated value 3.5A
Current range 0...3.5A
● Note
+45 ... +60 °C: Derating 2%/K
Active power supplied typical 105W
Parallel switching for enhanced performance Yes
Numbers of parallel switchable units for enhanced
performance
2
Efficiency
Efficiency at Vout rated, Iout rated, approx. 80%
Power loss at Vout rated, Iout rated, approx. 27W
Protection and monitoring
Output overvoltage protection Yes, according to EN 60950-1
Current limitation 4.9A
Current limitation Limit point < 4.9 A; switch-off point < 6 A
Property of the output Short-circuit proof Yes
Short-circuit protection Electronic shutdown, automatic restart
Overload/short-circuit indicator -
Safety
Primary/secondary isolation Yes
Galvanic isolation Safety extra low output voltage Vout according to EN 60950-1
Protection class Class I
Leakage current maximum 3.5mA
CE mark Yes
UL/CSA approval Yes
6EP1353-0AA00 Changes preserved
Page 2/
3
13.03.2015 © Copyright Siemens AG