Datasheet

Protection and monitoring
Output overvoltage protection Yes, according to EN 60950-1
Current limitation, typ. 21 A
Characteristic feature of the output / short-circuit protected Yes
Short-circuit protection Electronic shutdown, automatic restart
Enduring short circuit current / Effective level / maximum 7 A
Enduring short circuit current / Effective level / typical
• Note overload capability 150 % Iout rated up to 5 s/min
Overload/short-circuit indicator -
Safety
Primary/secondary isolation Yes
Potential separation Safety extra-low output voltage Uout acc. to EN 60950-1 and EN
50178
Protection class Class I
stray current / maximum 3.5 mA
stray current / typical 1 mA
CE mark Yes
UL/CSA approval Yes
UL/cUL (CSA) approval cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; in
preparation: cCSAus (CSA C22.2 No. 60950-1, UL 60950-1)
Explosion protection ATEX (EX) II 3G Ex nA nC IIC T4 Gc; cCSAus (CSA C22.2 No. 213,
ANSI/ISA-12.12.01) Class I, Div. 2, Group ABCD, T4
FM approval -
CB approval Yes
Marine approval GL
Degree of protection (EN 60529) IP20
EMC
Emitted interference EN 55022 Class B
Supply harmonics limitation EN 61000-3-2
Noise immunity EN 61000-6-2
Operating data
Ambient temperature / in operation 0 … 70 °C
• Note with natural convection
Ambient temperature / on transport -40 … +85 °C
Ambient temperature / in storage -40 … +85 °C
Humidity class according to EN 60721 Climate class 3K3, no condensation
Mechanics
Connection technology screw-type terminals
Connections / Supply input L1, N, PE: 1 screw terminal each for 0.2 ... 4 mm² single-core/finely
stranded
Connections / Output +, -: 2 screw terminals each for 0.2 ... 4 mm²
6EP1336-2BA10
Page 3/ 04/04/2014
subject to modifications
© Copyright Siemens AG 2014
4