Datasheet
Built-in incoming fuse T 10 A (not accessible)
Protection in the mains power input (IEC 898) Recommended miniature circuit breaker: from 10 A characteristic C
or circuit-breaker 3RV2411-1JA10 (120 V) or 3RV2411-1FA10 (230
V)
Output
Output Controlled, isolated DC voltage
Rated voltage Vout DC 24 V
Total tolerance, static ± 3 %
Static mains compensation, approx. 0.5 %
Static load balancing, approx. 1 %
Residual ripple peak-peak, max. 150 mV
Spikes peak-peak, max. (bandwidth: 20 MHz) 240 mV
Adjustment range 24 … 28 V
Product feature / output voltage adjustable Yes
Output voltage setting via potentiometer
• Note max. 480 W
Status display Green LED for 24 V OK
Signaling Relay contact (NO contact, rating 50 V DC/ 0.3 A) for "24 V OK"
On/off behavior No overshoot of Vout (soft start)
Startup delay, max. 1.5 s
Voltage rise, typ. 50 ms
Voltage increase time / of the output voltage / maximum 500 ms
Rated current value Iout rated 20 A
Current range 0 … 20 A
• Note 24 A up to +45°C; +60 ... +70 °C: Derating 5%/K
delivered active power / typ. 480 W
short-term overload current / at short-circuit during run-up / typical 35 A
Duration of overloading ability for excess current / on short-circuiting
during the start-up
100 ms
short-term overload current / at short-circuit during operation / typical 35 A
Duration of overloading ability for excess current / on short-circuiting
during the operational phase
100 ms
Parallel switching for enhanced performance Yes
Numbers of parallel switchable units for enhanced performance 2
Efficiency
Efficiency at Vout rated, Iout rated, approx. 90 %
Power loss at Vout rated, Iout rated, approx. 53 W
Closed-loop control
Dynamic mains compensation (Vin rated ±15 %), max. 1 %
Dynamic load smoothing (Iout: 50/100/50 %), Uout ± typ. 3 %
Setting time / maximum 10 ms
6EP1336-2BA10
Page 2/ 04/04/2014
subject to modifications
© Copyright Siemens AG 2014
4