Datasheet
● at rated input voltage 230 V
2.4A
● at rated input voltage 500 V
1.1A
Switch-on current limiting (+25 °C), max. 35A
I²t, max. 4A²·s
Built-in incoming fuse T 6.3 A (not accessible)
Protection in the mains power input (IEC 898) Recommended miniature circuit breaker at 1-phase operation:
from 6 A (10 A) characteristic C (B); required at 2-phase
operation: circuit breaker 2-pole connected or circuit breaker
3RV2011-1EA10 (setting 3.8 A) or 3RV2711-1ED10 (UL 489) at
230 V; 3RV2011-1DA10 (setting 3 A) or 3RV2711-1DD10 (UL
489) at 400/500 V
Output
Output Controlled, isolated DC voltage
Rated voltage Vout DC 24V
Total tolerance, static ± 3%
Static mains compensation, approx. 0.1%
Static load balancing, approx. 0.1%
Residual ripple peak-peak, max. 50mV
Spikes peak-peak, max. (bandwidth: 20 MHz) 200mV
Adjustment range 24...28.8V
Product function Output voltage adjustable Yes
Output voltage setting via potentiometer
Status display Green LED for 24 V OK
Signaling Relay contact (NO contact, rating 60 V DC/ 0.3 A) for "24 V OK"
On/off behavior Overshoot of Vout approx. 3 %
Startup delay, max. 1s
Voltage rise, typ. 50ms
Rated current value Iout rated 10A
Current range 0...10A
● Note
+60 ... +70 °C: Derating 2%/K (at 120 V, 230 V) or 3.5%/K (at 400
V)
Supplied active power typical 240W
Short-term overload current
● at short-circuit during operation typical
30A
Duration of overloading capability for excess current
● at short-circuit during operation
25ms
Constant overload current
● on short-circuiting during the start-up typical
12A
Parallel switching for enhanced performance Yes; switchable characteristic
Numbers of parallel switchable units for enhanced
performance
2
Efficiency
Efficiency at Vout rated, Iout rated, approx. 91%
6EP1334-3BA10-8AB0 Subject to change without notice
Page 2/
4
04/16/2018 © Copyright Siemens