Current limitation 3 … 3.4 A
Characteristic feature of the output / short-circuit protected Yes
Short-circuit protection Constant current characteristic
Enduring short circuit current / Effective level / typical 3.4 A
• Note overload capability 150 % Iout rated up to 5 s/min
Overload/short-circuit indicator -
Safety
Primary/secondary isolation Yes
Potential separation Safety extra-low output voltage Uout acc. to EN 60950-1 and EN
50178
Protection class Class I
stray current / maximum 3.5 mA
stray current / typical 0.4 mA
CE mark Yes
UL/CSA approval Yes
UL/cUL (CSA) approval cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259,
cCSAus (CSA C22.2 No. 60950-1, UL 60950-1, UL 1604)
Explosion protection ATEX and UL 1604 Class I, Div. 2, Group ABCD in preparation
FM approval -
CB approval Yes
Marine approval GL in process
Degree of protection (EN 60529) IP20
EMC
Emitted interference EN 55022 Class B
Supply harmonics limitation not applicable
Noise immunity EN 61000-6-2
Operating data
Ambient temperature / in operation -10 … +70 °C
• Note with natural convection
Ambient temparature / on transport -40 … +85 °C
Ambient temparature / in storage -40 … +85 °C
Humidity class according to EN 60721 Climate class 3K3, no condensation
Mechanics
Connection technology screw-type terminals
Connections / Supply input L, N, PE: 1 screw terminal each for 0.5 ... 2.5 mm² single-core/finely
stranded
Connections / Output L+, M: 2 screw terminals each for 0.5 ... 2.5 mm²
Connections / Auxiliary Alarm signals: 2 screw terminals for 0.5 ... 2.5 mm²
Width / of the housing 32.5 mm
Height / of the housing 125 mm
6EP1332-2BA20