Datasheet

Protection in the mains power input (IEC 898) Recommended miniature circuit breaker: from 3 A, characteristic C
Output
Output Controlled, isolated DC voltage
Rated voltage Vout DC 24 V
Total tolerance, static ± 3 %
Static mains compensation, approx. 0.1 %
Static load balancing, approx. 1 %
Residual ripple peak-peak, max. 150 mV
Residual ripple peak-peak, typ. 30 mV
Spikes peak-peak, max. (bandwidth: 20 MHz) 240 mV
Spikes peak-peak, typ. (bandwidth: 20 MHz) 70 mV
Adjustment range 22.8 … 28 V
Product feature / output voltage adjustable Yes
Output voltage setting via potentiometer
Status display Green LED for 24 V OK
On/off behavior Overshoot of Vout < 3 %
Startup delay, max. 0.3 s
Voltage rise, typ. 15 ms
Rated current value Iout rated 2.5 A
Current range 0 … 3 A
• Note 1.75 A up to +70°C, 2.5 A up to +60 °C, 3 A up to +45 °C
delivered active power / typ. 60 W
short-term overload current / at short-circuit during run-up / typical 9 A
Duration of overloading ability for excess current / on short-circuiting
during the start-up
100 ms
short-term overload current / at short-circuit during operation / typical 9 A
Duration of overloading ability for excess current / on short-circuiting
during the operational phase
800 ms
Parallel switching for enhanced performance Yes
Numbers of parallel switchable units for enhanced performance 2
Efficiency
Efficiency at Vout rated, Iout rated, approx. 85 %
Power loss at Vout rated, Iout rated, approx. 10 W
Closed-loop control
Dynamic mains compensation (Vin rated ±15 %), max. 0.3 %
Dynamic load smoothing (Iout: 10/90/10 %), Uout ± typ. 3 %
Load step setting time 10 to 90%, typ. 1 ms
Load step setting time 90 to 10%, typ. 1 ms
Protection and monitoring
Output overvoltage protection < 33 V
6EP1332-2BA20
Page 2/ 11/01/2012
subject to modifications
© Copyright Siemens AG 2012
4