Datasheet

Protection and monitoring
Output overvoltage protection < 20 V
Current limitation 14...16.4A
Property of the output Short-circuit proof Yes
Short-circuit protection Constant current characteristic
Enduring short circuit current RMS value
● typical
16.4A
Overcurrent overload capability in normal operation overload capability 150 % Iout rated up to 5 s/min
Overload/short-circuit indicator -
Safety
Primary/secondary isolation Yes
Galvanic isolation Safety extra-low output voltage Uout acc. to EN 60950-1 and EN
50178
Protection class Class I
Leakage current
● maximum
3.5mA
● typical
0.8mA
CE mark Yes
UL/cUL (CSA) approval cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259;
cCSAus (CSA C22.2 No. 60950-1, UL 60950-1)
Explosion protection IECEx Ex nA nC IIC T4 Gc; ATEX (EX) II 3G Ex nA nC IIC T4 Gc;
cULus Class I Div. 2 (ANSI/ISA-12.12.01-2007, CSA C22.2 No.
213) Group ABCD, T4; cCSAus (CSA C22.2 No. 213, ANSI/ISA-
12.12.01) Class I, Div. 2, Group ABCD, T4
FM approval -
CB approval Yes
Marine approval DNV GL
Degree of protection (EN 60529) IP20
EMC
Emitted interference EN 55022 Class B
Supply harmonics limitation EN 61000-3-2
Noise immunity EN 61000-6-2
Operating data
Ambient temperature
● during operation
-25...+70°C
— Note
with natural convection
● during transport
-40...+85°C
● during storage
-40...+85°C
Humidity class according to EN 60721 Climate class 3K3, no condensation
Mechanics
Connection technology screw-type terminals
Connections
6EP1323-2BA00 Subject to change without notice
Page 3/
4
04/17/2018 © Copyright Siemens