User Manual
Technical data   
A.8 Technical data: LOGO! 12/24... LOGO! DM8 12/24R 
  LOGO! 
334  Manual, 04/2011, A5E03556174-01 
A.8  Technical data: LOGO! 12/24... LOGO! DM8 12/24R 
  LOGO! 12/24RC 
LOGO! 12/24RCo 
LOGO! 12/24RCE 
LOGO! DM8 12/24R 
Power supply 
Input voltage  12/24 V DC  12/24 V DC 
Permissible range  10.8 ... 28.8 V DC  10.8 ... 28.8 V DC 
Reverse polarity protection  Yes  Yes 
Power consumption 
•  12 V DC 
•  24 V DC 
•  60 ... 175 mA 
•  40 ... 100 mA 
•  30 ... 140 mA 
•  20 ... 75 mA 
Voltage failure buffering 
•  12 V DC 
•  24 V DC 
•  typ. 2 ms 
•  typ. 5 ms 
•  typ. 2 ms 
•  typ. 5 ms 
Power loss 
•  12 V DC 
•  24 V DC 
•  0.7 ... 2.1 W 
•  1.0 ... 2.4 W 
•  0.3 ... 1.7 W 
•  0.4 ... 1.8 W 
Backup of the real-time 
clock at 25 °C 
•  LOGO! 12/24RC/RCo: 
typ. 80 hours without battery card 
typ. 2 years with battery card 
•  LOGO! 12/24RCE: 
typ. 20 days 
- - 
Accuracy of the real-time 
clock 
typ. ± 2 s / day  - - 
Electrical isolation  No  No 
Digital inputs 
Number  8  4 
Electrical isolation  No  No 
Number of high speed inputs 4 (I3, I4, I5, I6)  0 
Input frequency 
•  Normal input 
•  High speed input 
•  Max. 4 Hz 
•  Max. 5 kHz 
•  max. 4 Hz 
•  - - 
Max. continuous permissible 
voltage 
28.8 V DC  28.8 V DC 
Input voltage L+ 
•  Signal 0 
•  Signal 1 
•  < 5 V DC 
•  > 8.5 V DC 
•  < 5 V DC 
•  > 8.5 V DC 