  Technical data 
  A.6 Technical data: LOGO! 24RC... 
LOGO! 
Manual, 04/2011, A5E03556174-01 
331 
  LOGO! 24RC 
LOGO! 24RCo 
Range  - - 
max. Input voltage  - - 
Digital outputs 
Number  4 
Output type  Relay outputs 
Electrical isolation  Yes 
In groups of  1 
Control of a digital input  Yes 
Continuous current I
th
  max. 10 A per relay 
Surge current  max. 30 A 
Incandescent lamp load (25000 switching 
cycles) at 
1000 W 
Fluorescent tubes with ballast (25000 
switching cycles) 
10 x 58 W 
Fluorescent tubes, conventionally 
compensated (25000 switching cycles) 
1 x 58 W 
Fluorescent tubes, uncompensated (25000 
switching cycles) 
10 x 58 W 
Derating  none; across the entire temperature range 
Short circuit-proof cos 1  Power protection B16, 600A 
Short circuit-proof cos 0.5 to 0.7  Power protection B16, 900A 
Parallel output circuits for power increase  Not permitted 
Protection of output relay 
(if desired) 
max. 16 A, 
characteristic B16 
Switching rate  
Mechanical  10 Hz 
Ohmic load/lamp load  2 Hz 
Inductive load  0.5 Hz 
Notice: For fluorescent lamps with capacitors, the technical data of fluorescent lamp ballasts 
must also be considered. If the maximum allowed surge current is exceeded, fluorescent 
lamps must be switched with appropriate contactor relays. 
The data was determined with the following devices: 
Siemens fluorescent tubes 58W VVG 5LZ 583 3-1 uncompensated. 
Siemens fluorescent tubes 58W VVG 5LZ 583 3-1 parallel compensated with 7μF. 
Siemens fluorescent tubes 58W VVG 5LZ 501 1-1N with ballast. 