User Manual
  Getting started with LOGO! 
LOGO! 
Manual, 04/2011, A5E03556174-01 
25 
Expansion modules 
The following expansion modules can be connected to LOGO!: 
Symbol  Name  Power supply  Inputs  Outputs 
LOGO! DM8 12/24R  12/24 V DC  4 digital  4 relays (5A) 
LOGO! DM8 24  24 V DC  4 digital  4 solid state 24V / 
0.3A 
LOGO! DM8 24R 
3)
  24 V AC/DC  4 digital  4 relays (5A) 
LOGO! DM8 230R  115 ... 240 V AC/DC  4 digital 
1)
  4 relays (5A) 
LOGO! DM16 24  24 V DC  8 digital  8 solid state 
24V / 0.3A 
LOGO! DM16 24R  24 V DC  8 digital  8 relays (5A) 
LOGO! DM16 230R  115 ... 240 V AC/DC  8 digital 
4)
  8 relays (5A) 
LOGO! AM2  12/24 V DC  2 analog 
0 ... 10V or 
0/4 ... 20mA 
2)
None 
LOGO! AM2 PT100  12/24 V DC  2 PT100 
6)
-50 degrees C to 
+200 degrees C 
None 
LOGO! AM2 RTD  12/24 V DC  2 PT100 or 2 PT1000 
or 1 PT100 plus 1 
PT1000 
6)
-50 degrees C to 
+200 degrees C 
None 
LOGO! AM2 AQ  24 V DC  None  2 analog 
0 ... 10 V DC or 
0/4...20mA 
5)
1)
  Different phases are not allowed within the inputs. 
2)
  0 ... 10 V, 0/4 ... 20 mA can be connected optionally. 
3)
  Digital inputs can be operated either with P or with N action. 
4)
  Two groups consisting of 4 inputs each. Each input within a group must be connected to the same 
phase. It is possible to interconnect groups with a different phase. 
5)
  0 ... 10 V, 0/4 ... 20 mA can be connected optionally. The 0/4 ... 20 mA current output is only 
possible with the LOGO! 0BA6 Base Module. 
6)
  Sensors supported by the LOGO! AM2 RTD module are the PT100 and PT1000 sensors with a 
default temperature coefficient α of 0.003850. 