LOGO! functions   
4.4 Special functions list - SF 
  LOGO! 
230  Manual, 04/2011, A5E03556174-01 
Status diagram 
Par  Q
n-1
 S  R  Trg  Q
n
*  0  0  0  0  0 
*  0 0 0 0 ->1 1** 
*  0  0  1  0  0 
*  0  0  1  0 ->1  0 
*  0  1  0  0  1 
*  0  1  0  0 ->1  1 
RS 0 1 1 0 0 
RS 0 1 1 0 ->1 0 
SR 0 1 1 0 1 
SR 0 1 1 0 ->1 1 
*  1  0  0  0  1 
*  1 0 0 0 ->1 0** 
*  1  0  1  0  0 
*  1  0  1  0 ->1  0 
*  1  1  0  0  1 
*  1  1  0  0 ->1  1 
RS 1 1 1 0 0 
RS 1 1 1 0 ->1 0 
SR 1 1 1 0 1 
SR 1 1 1 0 ->1 1 
*: RS or SR 
**: Triggering signal is effective, because S and R = 0. 
Depending on your configuration, either input R takes priority over input S (input S is not 
effective when R = 1), or vice versa (input R is not effective when S = 1). 
After a power failure, the pulse relay and output Q are reset if you have not enabled 
retentivity. 
View in programming mode: 
3DU 56
%5
3DU 65
%5
3UHVV
Ⴃ
RU
Ⴍ
This special function is not available in parameter assignment mode. 
Note 
If Trg = 0 and Par = RS, the special function "Pulse relay" corresponds with the special 
function "Latching relay (Page 228)". 