If your LOGO! is a LOGO! 0BA7, you can additionally use the actual values of the following 
functions: 
●  Analog filter (0BA7 only) (Page 271) (actual value AQ) 
●  Average value (0BA7 only) (Page 276) (actual value AQ) 
●  Max/Min (0BA7 only) (Page 273) (actual value AQ) 
●  On-delay (Page 160) (current time Ta) 
●  Off-delay (Page 164) (current time Ta) 
●  On-/off-delay (Page 166) (current time Ta) 
●  Retentive on-delay (Page 168) (current time Ta) 
●  Wiping relay(pulse output) (Page 170) (current time Ta) 
●  Edge triggered wiping relay (Page 172) (current time Ta) 
●  Asynchronous pulse generator (Page 175) (current time Ta) 
●  Stairway light switch (Page 179) (current time Ta) 
●  Multiple func
tion switc
h (current time Ta) 
● 
Stopwatch (Page 198) (actual value AQ) 
●  Threshold trigger (Page 210) (actual value Fre) 
Select the require
d function by the block number. The timebase is configurable. For 
information on valid ranges and parameter defaults, refer to the On-delay (Page 160) topic. 
Timing diagram 
7
7/
7/ 7/
7UJ
4
7
7DLVEXV\
Functional description 
A 0 to 1 transition at input Trg sets output Q. 
If output Q = 0, and input Trg is set hi at least for the duration of T
L
, the permanent lighting 
function is enabled and output Q is set accordingly. 
The off-delay T is triggered when input Trg returns to 0 before T
L
 has expired. 
Output Q is reset when T
a 
= T. 
You can output an off-warning signal prior to the expiration of the off-delay time (T - T
!
) that 
resets Q for the duration of the prewarning time period T
!L
. A subsequent signal at Trg 
always resets T and the output Q. 
If retentivity is not set, output Q and the expired time are reset after a power failure. 