Data Sheet
Operating voltage / of the signaling contacts
● at DC / Rated value
24V
Operating current / of the signaling contacts
● at DC / maximum
0.1A
Supply voltage, current consumption, power loss
Type of voltage / of the supply voltage DC
Supply voltage
● external
24V
● external / minimum
18V
● external / maximum
32V
Product component / fusing at power supply input Yes
Fuse protection type / at input for supply voltage 1.1 A / 33 V
Consumed current / maximum 0.33A
Power loss [W]
● at DC / at 24 V
7.92W
Permitted ambient conditions
Ambient temperature
● during operation
-40...+60°C
● during storage
-40...+70°C
● during transport
-40...+70°C
Relative humidity
● at 25 °C / without condensation / during
operation / maximum
100%
● with condensation / maximum
100%; rel. humidity, incl. condensation/frost permissible (no
commissioning in condensed state)
Ambient condition / relating to ambient temperature -
air pressure - installation altitude
-40 ... +60 °C at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // -40
... +50 °C at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // -40 ...
+40 °C at 658 hPa ... 540 hPa (+3500 m ... +5000 m)
Resistance to biologically active substances /
conformity acc. to EN 60721-3-3
Yes; Compliance with EN 60721-3-3, Class 3B2 mold, fungus,
and sponge spores (except fauna). The supplied plug covers must
remain in place over the unused interfaces during operation!
Resistance to chemically active substances /
conformity acc. to EN 60721-3-3
Yes; Compliance with EN 60721-3-3, class 3C4 incl. salt spray
according to EN 60068-2-52 (severity 3). The supplied plug
covers must remain in place over the unused interfaces during
operation!
Resistance to mechanically active substances /
conformity acc. to EN 60721-3-3
Yes; Compliance with EN 60721-3-3, Class 3S4 including sand,
dust. The supplied plug covers must remain in place over the
unused interfaces during operation!
Protection class IP IP30
Design, dimensions and weight
Design compact
Width 120mm
Height 125mm
6AG1212-2BB00-4AA3 Subject to change without notice
Page 2/
5
08/27/2019 © Copyright Siemens