Specifications
Overcurrent Protection SIPROTEC 7SJ81
5/6 SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 3
1
2
3
4
5
6
7
8
9
10
for Low-Power CT and VT Applications – Application sheets
Protection functions
Overcurrent protection (ANSI 50, 50N, 51, 51N)
This function is based on the phase-selective measurement
of the three phase currents and the ground current (four
transformers). Three defi nite time-overcurrent protection
elements (DMT) are available both for the phase and the
ground elements. The current threshold and the delay time
can be set in a wide range.
Inverse time-overcurrent protection characteristics (IDMTL)
can also be selected and activated.
Reset characteristics
Time coordination with electromechanical relays is made
easy with the inclusion of the reset characteristics according
to ANSI C37.112 and IEC 60255-3/BS 142 standards. When
using the reset characteristic (disk emulation), the reset pro-
cess is initiated after the fault current has disappeared. This
reset process corresponds to the reverse movement of the
Ferraris disk of an electromechanical relay (disk emulation).
Available inverse-time characteristics
Characteristics acc. to IEC 60255-3 ANSI/IEEE
Inverse
Short inverse
Long inverse
Moderately inverse
Very inverse
Extremely inverse
Table 5/2 Available inverse-time characteristics
Inrush restraint
If second harmonic content is detected during the energi-
zation of a transformer, the pickup of stages I >, I
p
, I >
dir
and I
p
dir
is blocked.
Dynamic settings group switching
In addition to the static parameter changeover, the pickup
thresholds and the tripping times for the directional and
non-directional time-overcurrent protection functions can
be changed over dynamically. As changeover criterion, the
circuit-breaker position, the prepared auto-reclosure, or a
binary input can be selected.
Directional comparison protection (cross-coupling)
It is used for selective instantaneous tripping of sections
fed from two sources, i.e. without the disadvantage of time
delays of the set characteristic. The directional comparison
protection is suitable if the distances between the protection
zones are not signifi cant and pilot wires are available for
signal transmission. In addition to the directional comparison
protection, the directional coordinated time-overcurrent
protection is used for complete selective backup protection.
Directional time-overcurrent protection (ANSI 67, 67N)
Directional phase and ground protection are separate func-
tions. They operate in parallel to the non-directional overcur-
rent elements. Their pickup values and delay times can be set
separately. Defi nite-time and inverse-time characteristics are
offered. The tripping characteristic can be rotated by ± 180
degrees.
By making use of the voltage memory, the directionality can
be determined reliably even for close-in (local) faults. If the
primary switching device closes onto a fault and the voltage
is too low to determine direction, the direction is determined
using voltage from the memorized voltage. If no voltages are
stored in the memory, tripping will be according to the set
characteristic.
For ground protection, users can choose whether the direc-
tion is to be calculated using the zero-sequence or negative-
sequence system quantities (selectable). If the zero-sequence
voltage tends to be very low due to the zero-sequence impe-
dance it will be better to use the negative-sequence quantities.
Fig. 5/4 Directional characteristics of the directional
time-overcurrent protection
(Sensitive) directional ground-fault detection
(ANSI 59N/64, 67Ns, 67N)
For isolated-neutral and compensated networks, the direc-
tion of power fl ow in the zero sequence is calculated from
the zero-sequence current I
0
and zero-sequence voltage V
0
.
For networks with an isolated neutral, the reactive current
component is evaluated; for compensated networks, the
active current component or residual resistive current is eva-
luated. For special network conditions, e.g. high-resistance
grounded networks with ohmic-capacitive ground-fault
current or low-resistance grounded networks with ohmic-
inductive current, the tripping characteristics can be rotated
approximately ± 45 degrees (see Fig.5/5).
Two modes of ground-fault direction detection can be
implemented: tripping or “signalling only mode”.










