Specifications

Line Differential Protection SIPROTEC 7SD80
3/6 SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 3
Application sheets
Protection functions
Differential protection (ANSI 87L, 87N L, 87Ns L)
The differential protection SIPROTEC 7SD80 consists of two
separately operating differential protection algorithms:
Phase comparison protection (PCP)
Earth-fault differential protection (EFD).
The phase comparison protection, PCP, offers a safe and
robust short-circuit protection for all types of neutral treat-
ment. Of course, this is also valid for application in systems
with isolated or resonant-earthed neutral. Adaptation of
the phase comparison protection according to the neutral
treatment is done by setting parameters via DIGSI.
The earth-fault differential protection, EFD, operates with
two different algorithms, depending on the neutral treat-
ment in the power system to be protected.
For application in solidly, low-resistance or high-resistance
earthed systems, the EFD analyzes the measured zero-se-
quence current. The fundamental wave of the zero-sequence
current is determined by ltering. The ltered zero-sequence
currents of the local side and the opposite side are added
and provide the zero-sequence differential current. The ad-
aptive stabilizing facilitates the parameterization and assured
stability and selectivity.
For application in power systems with isolated or resonant-
earthed neutrals, the connection of voltages – at least of the
zero-sequence voltage – and the use of a sensitive earth-cur-
rent transformer is required. From the zero-sequence current
and the voltage, the apparent power of the zero-sequence
system is calculated, and compared with the opposite end.
Depending on the direction of the power ow, an internal or
external earth fault is detected. This is only indicated, and
can be shut down immediately or with a set delay.
Circuit-breaker intertripping (ANSI 85 DT)
The 7SD80 devices have an integrated circuit-breaker inter-
tripping function for tripping the circuit-breaker at the oppo-
site end. The circuit-breaker intertripping can be activated
directly by the differential protection functions, but also
through binary signals of any other external or internal pro-
tection function. The circuit-breaker intertripping can be
combined with an integrated phase and/or zero-sequence
current threshold, which permits to trip the circuit-breaker
if there is a suf ciently high current.
Overcurrent protection, non-directional/directional
(ANSI 50, 50N, 51, 51N, 67, 67N)
This function is based on the phase-selective measurement
of the three phase currents and the earth current (4 instru-
ment transformers).
In the SIPROTEC 7SD80, three de nite time-overcurrent
protection stages are integrated for protection against phase
faults, as well as for protection against earth faults. The current
threshold and the delay time can be set for each stage. Fur-
thermore, inverse time-overcurrent protection characteristics
can be added.
Each of the overcurrent protection stages can be set as emer-
gency or backup protection independently of each other. This
enables the integration of the SIPROTEC 7SD80 in a simple
busbar protection concept by means of reverse interlocking.
When voltage transformers are connected, a directional
time-overcurrent protection emergency function can be
activated if the protection interface communication fails.
Available inverse-time characteristics
Characteristics acc. to IEC 60255-3 ANSI/IEEE
Inverse

Short inverse
Long inverse

Moderately inverse
Very inverse

Extremely inverse

Tabelle 3/2 Available inverse-time characteristics
Inrush restraint
When the second harmonic is detected while energizing a
transformer inside or outside of the protection zone, pickup
of the differential protection stages or the overcurrent
protection stages can be suppressed.
Breaker failure protection (ANSI 50BF)
If a faulted portion of the electrical circuit is not disconnected
when a trip command is issued to a circuit-breaker, another
trip command can be initiated using the breaker failure protec-
tion which trips the circuit-breaker of an upstream feeder.
Breaker failure is detected if, after a trip command is issued
the current keeps on owing into the faulted circuit. It is also
possible to make use of the circuit-breaker position contacts
for indication as opposed to the current owing through the
circuit-breaker.
External trip initiation
Through a binary input, an external protection device or mo-
nitoring equipment can be coupled into the signal processing
of the SIPROTEC 7SD80 to trip the local circuit-breaker.
1
2
3
4
5
6
7
8
9
10