PVS 600Series 1 ___________________ Introduction 2 ___________________ Safety instructions SINVERT inverter Central inverter PVS 600Series Operating Instructions 3 ___________________ Description 4 ___________________ Grid management ___________________ 5 Application planning ___________________ 6 Installation ___________________ 7 Connecting ___________________ 8 Commissioning Operator control and ___________________ 9 monitoring Fault, alarm and system ___________________ 10 messages ________________
Legal information Warning notice system This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are graded according to the degree of danger.
Table of contents 1 2 3 4 Introduction ............................................................................................................................................. 9 1.1 Preface ...................................................................................................................................... 9 1.2 Recycling and disposal ...........................................................................................................10 Safety instructions ...............
Table of contents 5 6 7 4.2.2.6 4.2.2.7 Reactive power control in accordance with output voltage Q=f(U) ........................................ 59 Reactive power control according to active power cos φ (P)................................................. 62 4.3 4.3.1 4.3.2 4.3.3 4.3.4 4.3.5 4.3.6 Dynamic grid support ............................................................................................................. 64 Behavior in the case of voltage dips (low voltage ride through) ........
Table of contents 8 9 10 7.2 Cabling ..................................................................................................................................109 7.3 7.3.1 7.3.2 7.3.3 7.3.4 7.3.5 7.3.6 7.3.7 7.3.8 7.3.9 7.3.10 7.3.11 Connecting the individual cables ..........................................................................................110 Requirements ........................................................................................................................
Table of contents 11 12 13 14 10.4 Correction of the alarms ....................................................................................................... 167 10.5 Event messages................................................................................................................... 170 10.6 Messages of the operator panel .......................................................................................... 178 Maintenance ...................................................
Introduction 1.1 1 Preface Purpose of the manual These operating instructions contain all the information required for installing, commissioning, and operating PVS 600Series inverters.
Introduction 1.2 Recycling and disposal 1.2 Recycling and disposal Devices described in this programming manual can be recycled owing to the low content of noxious substances in their version. Please contact a certified waste disposal company for eco-friendly recycling and to dispose of your old devices.
Safety instructions 2.1 2 General safety instructions Note Please observe the legal information and the safety instructions on the back of the cover sheet of this documentation. Qualified personnel Installation, commissioning, operation and maintenance of this device must be carried out by qualified personnel only. ● The installation engineer must be qualified according to national guidelines. ● Approval by the relevant electrical utility may also be necessary.
Safety instructions 2.1 General safety instructions Modifications to the product Modifications to the SINVERT inverter may be made only if these have been explicitly approved by the system manufacturer. The manufacturer shall not be liable for any damage arising from unapproved modifications to the SINVERT inverter. Repairs Only authorized personnel are permitted to repair the device. Electrical voltages The PVS cabinets must be opened and worked on by qualified personnel only.
Safety instructions 2.2 Health and safety at work 2.2 Health and safety at work It is essential that you adhere to the health and safety regulations, e.g. VDE 105-1/EN 50110-1 (Operation of Electrical Installations), which apply at the relevant installation site.
Safety instructions 2.3 Hazards during handling and installation 2.3 Hazards during handling and installation Improper handling and installation of certain parts and components can result in injury under unfavorable conditions. CAUTION Danger of injury due to improper handling! Injury by crushing, jackknifing, cutting, bumping, or lifting! • The general construction and safety regulations must be observed in handling and installation. • Each cabinet section weighs more than 1,000 kg.
Safety instructions 2.5 Incorrect grid monitoring parameters 2.5 Incorrect grid monitoring parameters NOTICE Withdrawal of operating permit If you operate the SINVERT PVS inverter with the wrong grid monitoring parameters, the electrical utility can withdraw your operating permit. The device must therefore only be commissioned by authorized service personnel. The system settings must be adapted to local requirements regarding grid monitoring parameters.
Safety instructions 2.7 Security information 2.7 Security information Siemens provides products and solutions with industrial security functions that support the secure operation of plants, solutions, machines, equipment and/or networks. They are important components in a holistic industrial security concept. With this in mind, Siemens’ products and solutions undergo continuous development. Siemens recommends strongly that you regularly check for product updates.
Description 3 The inverter of the SINVERT PVS device line is used in medium and large PV plants and converts the DC current of the PV generators into AC current. This AC current is then fed into the connected power grid. The SINVERT PVS inverter design is optimized for the lowest possible losses and thus the greatest possible efficiency. Figure 3-1 Installation overview The integrated DC and AC distribution makes the system compact and cheap to integrate.
Description 3.1 Features 3.
Description 3.2 Design 3.2 Design Inverter subunit and inverter unit An inverter subunit always consists of a DC cabinet and an AC cabinet. A complete inverter unit can comprise up to 4 inverter subunits (DC/AC cabinets) that are also referred to as master-slave combinations (see Chapter Master-slave combinations (Page 22)).
Description 3.2 Design The figure below shows the higher-level function units of the inverter subunit with open doors.
Description 3.3 Operating principle 3.3 Operating principle The SINVERT PVS inverter works on the following functional principles: ● The inverters are based on SINAMICS (power unit with IGBT three-phase bridge) and SIMOTION (controller). ● 3 inputs for connecting the PV array are provided at the PV array end. Note The PV array must be connected for this purpose in 3 sub-arrays with the same total current and voltage values. ● The 3 inputs on the DC side are equipped with LV HRC fuses and DC contactors.
Description 3.4 Master-slave combinations 3.4 Master-slave combinations A SINVERT PVS inverter subunit is available in two versions: ● Master ● Slave The combination of a master unit and one or more slave unit(s) results in a master/slave combination. Master The master comprises a DC cabinet and an AC cabinet with touch panel. A master with a touch panel is required in every configuration. The master or the entire installation can be operated and monitored via the touch panel.
Description 3.
Description 3.4 Master-slave combinations Slave The slave comprises a DC cabinet and an AC cabinet without touch panel. Since the slave does not have its own touch panel, it can only be operated and monitored using an associated master or its touch panel.
Description 3.
Description 3.4 Master-slave combinations Master/slave combinations The inverters of the SINVERT PVS500, PVS585, PVS600 or PVS630 series can be used as single devices or in combination with other inverter subunits in a master/slave combination. Such a combination always has a master and can additionally contain up to three slaves. The following master/slave combinations are available.
Description 3.
Description 3.5 Inverter options 3.5 Inverter options The following functional expansions and options are available for the PVS 600Series: Option Option identifier on the nameplate PV array grounding - positive-pole grounding PV field grounding positive pole PV array grounding - negative-pole grounding PV field grounding negative pole Increase in max. DC voltage to 1 000 V Max.
Description 3.5 Inverter options 3.5.1 PV array grounding With the optional feature "Positive / Negative PV array Grounding", the SINVERT inverters offer an ideal choice for manufacturers who require a module ground.
Description 3.5 Inverter options Negative-pole grounding Grounding an active conductor (negative pole) means that the inverter's insulation measuring function no longer works in the normal way. A hazardous current can start to flow as soon as the first insulation damage occurs. For this reason, the condition of the system is monitored through measurement of the current between the negative pole and ground.
Description 3.5 Inverter options Switching on the PV inverter with "1000 V option" Switching on the PVS allows a variable voltage divider, consisting of series and parallel resistors, to activate the inverter DC link (without closing the DC input contactors). Thus only the required fraction of the PV field no-load voltage is present at the DC link, and not the entire PV field no-load voltage. The upstream measurement of the PV field voltage (Upv) is carried out in each individual inverter subunit.
Description 3.6 System components 3.6 System components The system components and accessories are used for optimal, flexible, and customized implementation of photovoltaic plants covering all aspects of the SINVERT PVS inverters, as well as expanding the functionality of the overall system.
Description 3.6 System components Monitoring and parameterization software ● SINVERT ConfigTool SINVERT ConfigTool is a free software program designed for configuring, parameterizing, and diagnosing inverters for photovoltaic installations. ● WinCC With our WinCC SCADA system, we offer you user-friendly monitoring and control of your entire photovoltaic plant.
Description 3.
Grid management 4.1 4 Grid management in the case of SINVERT PVS The following options are available for complying with requirements regarding grid safety management: ● Parameterization of the functions in the SINVERT PVS inverter The functions/specifications can be set manually via parameters in the SINVERT PVS inverter. ● Parameterization of the functions using the SINVERT PVS ControlBox The SINVERT PVS ControlBox is used to control the SINVERT PVS inverters of a PV plant.
Grid management 4.1 Grid management in the case of SINVERT PVS Technical requirements of the inverter The grid requirements are divided into static grid support, decoupling protection, and dynamic grid support. To meet the requirements of grid operators, you also require a plant controller such as a SINVERT PVS ControlBox, in addition to the functions in the SINVERT PVS inverter.
Grid management 4.1 Grid management in the case of SINVERT PVS Interface to the grid operator Communication with the grid operator is achieved via a SINVERT PVS ControlBox. The ControlBox measures at the infeed point and controls the individual inverters in accordance with the grid operator's specifications.
Grid management 4.2 Static grid support 4.2 Static grid support 4.2.
Grid management 4.2 Static grid support 4.2.1.1 Active power control to fixed setpoint Function The active power of the SINVERT PVS inverter can be limited to a fixed setpoint Pmax. The setting is made as a percentage of the maximum rated power. This function is also used by the SINVERT PVS ControlBox to implement the grid operator's specifications. Note SINVERT PVS ControlBox When using the SINVERT PVS ControlBox, this value is overwritten cyclically.
Grid management 4.2 Static grid support You activate or deactivate the active power control to a fixed setpoint using the following three parameters: Parameter number Parameters Range Increment 33837 Activation 1 of Pmax controller On - 33838 Activation 2 of Pmax controller On Off - Off For activating the active power control to a fixed setpoint, both parameters must be set to "On". For "Active power control to fixed setpoint", enter the setpoint in the field p32828. 4.2.1.
Grid management 4.2 Static grid support Resumption of normal operation: There are three modes of resuming normal operation in the the case of frequency derating: 1. Frequency derating without hysteresis Figure 4-6 Active power control according to frequency P=f(f) without hysteresis As long as the frequency does not drop below the limit f1 again, the SINVERT PVS inverter supplies an output power dependent on the level of the current frequency along the curve.
Grid management 4.2 Static grid support 3. Frequency derating with hysteresis and without start frequency Figure 4-8 Active power control according to frequency P=f(f) with hysteresis and start frequency Contrary to active power control according to frequency P=f(f) with hysteresis and start frequency, the second limit frequency f2 is not required.
Grid management 4.2 Static grid support Settings Figure 4-9 Frequency derating [1/1] The function can be set via the following parameters: Parameter number Parameters Range Increment 33805 Activation of FB FControl On - Frequency Derating Mode 1. Hysteresis with start frequency 32320 Off - 2. Hysteresis without start frequency 3. No hysteresis 32624 Limit frequency f1 50 Hz: 47 ... 53 Hz 60 Hz: 57 ... 62 Hz 0.01 Hz 32627 Limit frequency f2 50 Hz: 47 ... 53 Hz 60 Hz: 57 ... 62 Hz 0.
Grid management 4.2 Static grid support Example of setting a frequency reduction without hysteresis Figure 4-10 Example of setting a frequency reduction without hysteresis Pf = 100% f1 = 50.2 Hz f2 > fH ⇒ f2 = fH +0.1 Hz f3 = 50.05 Hz fH > 52.2 Hz ⇒ fH = 52.2 Hz +0.1 Hz Example of setting a frequency reduction with hysteresis Figure 4-11 Example of setting a frequency reduction with hysteresis Pf = 100% Pf2 = 60% f1 = 50.2 Hz f2 = 51.2 Hz f3 = 50.05 Hz fH = 51.
Grid management 4.2 Static grid support 4.2.1.3 Active power control in accordance with output voltage P = f(U) Function The active power of the SINVERT PVS inverter can be reduced dependent on the output voltage. If the voltage exceeds a parameterized voltage limit UH, see Chapter Voltage monitoring (Page 76), the SINVERT PVS inverter switches off. PU Actual active power Figure 4-12 Active power control according to output voltage P = f(U) Note The function can be deactivated if required.
Grid management 4.2 Static grid support Settings Figure 4-13 P & Q control [3/9] The function can be activated or deactivated via the following parameters: Parameter number Parameters 33842 Activation of characteristic Pmax(U) Range Increment On - Off You can find the setting options for UH in Chapter Voltage monitoring (Page 76). 4.2.1.
Grid management 4.2 Static grid support Figure 4-14 Active power control during the switch-on operation Figure 4-15 Active power ramps [1/1] Settings The function can be set via the following parameter: Parameter number Parameters Range 32330 Type of ramp • No ramp (ramp deactivated) • Ramp after grid fault (standard) • INV start always with ramp 32331 Gradient of the increase 1 ...
Grid management 4.2 Static grid support 4.2.2 Reactive power control Methods of controlling the reactive power The increasingly strong trend towards integration of distributed generating plants into distribution grids results in the rising challenge of voltage stability. It is possible to influence the grid voltage by means of the reactive power. The SINVERT PVS inverters can be operated with a reactive power corresponding to a power factor cosφ = 0.
Grid management 4.2 Static grid support Reactive power control on the basis of reactive power Q For reactive power Q (setpoint type), you can select one of the following functions (setpoint source): ● Absolute fixed setpoint ● Q (U) curve ● Q (t) curve ● Relative fixed setpoint Note SINVERT PVS ControlBox When using the SINVERT PVS ControlBox, the function "Absolute fixed setpoint" must be selected since the fixed setpoint is specified by the SINVERT PVS ControlBox.
Grid management 4.
Grid management 4.2 Static grid support 4.2.2.1 Reactive power control to fixed setpoint Q absolute Function The reactive power of the SINVERT PVS inverter can be set to a fixed setpoint. The inverter can provide reactive power for voltage support/reduction. This can be achieved either on the basis of a fixed reactive power value or on the basis of a fixed power factor. Note SINVERT PVS ControlBox When using the SINVERT PVS ControlBox, this value is overwritten cyclically. Settings 1.
Grid management 4.2 Static grid support The function can be set via the following parameters: 4.2.2.
Grid management 4.2 Static grid support 4. Enter the setpoint for the maximum reactive power in field p33104. If the reactive power must be limited to a lower value than the maximum possible value, you can enter this value here. Otherwise, the default value should remain.
Grid management 4.2 Static grid support 4.2.2.3 Reactive power control to fixed setpoint cos phi Function The reactive power of the SINVERT PVS inverter can be set to a fixed setpoint. The inverter can provide reactive power for voltage support/reduction. This can be achieved either on the basis of a fixed reactive power value or on the basis of a fixed power factor. Note SINVERT PVS ControlBox When using the SINVERT PVS ControlBox, this value is overwritten cyclically. Settings 1.
Grid management 4.2 Static grid support The function can be set via the following parameters: 4.2.2.4 Function Parameter number Parameters 33833 Selection of setpoint source Range • Fixed setpoint • cos φ(t) • cos φ(P) Increment - 32812 Power factor -0.8 … 1 … 0.
Grid management 4.2 Static grid support Settings Figure 4-22 P & Q control [2/9] Figure 4-23 P & Q control [4/9] The function can be set via the following parameters: Parameter number Parameters Range Increment 33101 t0 ... t23 00:00:00 ... 23:59:59 1s 33100 Reactive power Q Dependent on the inverter type, see table below 0.
Grid management 4.2 Static grid support Note System time The system time on the SINVERT PVS inverter must be correctly set. Note SIMOTION D425 time Please note the possible time deviation of the SIMOTION D425. You can find information on the accuracy of the real-time clock of the SIMOTION D425 in the SIMOTION D4x5 manual. You can find the SIMOTION D4x5 manual in the Industry Online Support (http://support.automation.siemens.com). 4.2.2.
Grid management 4.2 Static grid support Settings Figure 4-25 P & Q control [2/9] Figure 4-26 P & Q control [5/9] The function can be set via the following parameters: Parameter number Parameters Range Increment 33103 t0 ... t23 00:00:00 ... 23:59:59 1s 33102 cos φ1 ... cos φ23 0,8ind ... 1 ... 0.8cap 0,001 Note Setpoints (p33102) Negative values correspond to an inductive reactive power (overexcited operation) and positive values to a capacitive reactive power (underexcited operation).
Grid management 4.2 Static grid support Note SIMOTION D425 time Please note the possible time deviation of the SIMOTION D425. You can find information on the accuracy of the real-time clock of the SIMOTION D425 in the SIMOTION D4x5 manual. You can find the SIMOTION D4x5 manual in the Industry Online Support (http://support.automation.siemens.com). 4.2.2.
Grid management 4.
Grid management 4.2 Static grid support The function can be set via the following parameters: Parameter number Parameters Range Increment 32688 Lower reactive power value Q2 0 … 100% of the maximum reactive power 0.01 % 32689 Lower reactive power value Q1 0 … 100% of the maximum reactive power 0.01 % 32690 Upper reactive power value Q3 0 … 100% of the maximum reactive power 0.01 % 32691 Upper reactive power value Q4 0 … 100% of the maximum reactive power 0.
Grid management 4.2 Static grid support 4.2.2.7 Reactive power control according to active power cos φ (P) Function The SINVERT PVS inverters can feed reactive power into the grid dependent on the level of the actual active power P (power factor/power curve cos φ (P)). The curve can be parameterized via two limit values. The limit values are specified as percentages of the rated power. The maximum cos φ1 (= - cos φ2) can also be parameterized.
Grid management 4.2 Static grid support Settings Figure 4-32 P & Q control [2/9] The function can be set via the following parameters: Parameter number Parameters Range Increment 32661 Lower power tolerance limit 10.0 ... 100.0 % 0.01 % of the rated power Upper power tolerance limit of the rated power 32660 100.0 ... 140.0 % 0.01 % 32615 Min. setpoint cos φ1 (= - cos φ2) -0.9 ... -0.8 0.01 32616 Max. setpoint cos φ1 (= - cos φ2) 0,8 ...
Grid management 4.3 Dynamic grid support 4.3 Dynamic grid support 4.3.1 Behavior in the case of voltage dips (low voltage ride through) Due to the growing spread of renewable energy forms, you must ensure that the inverter does not shut down immediately when brief voltage dips occur. The SINVERT PVS inverter has the ability to withstand brief voltage dips and remain on the grid.
Grid management 4.3 Dynamic grid support Settings Note the following points when parameterizing the LVRT curve: ● The parameterized LVRT curve must correspond to the undervoltage protection settings. For this reason, parameterize two of the interpolation points identically to the entered limit values of the undervoltage monitor. See Chapter Voltage monitoring (Page 76). ● When parameterizing, all fields must be filled, but it is not absolutely necessary to use all available interpolation points.
Grid management 4.3 Dynamic grid support The function can be set via the following parameters: Parameter number Parameters Range Increment 32075 LVRT activation On - 33140 LVRT mode Off 32090 LVRT reactive power response • Standard mode • Zero power mode • Q mode • k factor mode • Advanced mode - - 33111 Time t 0 ... 60000 ms 1 ms 33110 Voltage level U / UC 0 ... 100 % 0.
Grid management 4.3 Dynamic grid support 4.3.3 Reactive current provision in the event of voltage dips Function In the event of a voltage dip, the SINVERT PVS inverter can provide reactive current for voltage stability. The level of the reactive current ΔIB / In additionally fed in when a fault occurs results from the depth of the grid voltage dip ΔU / Un and the k factor. No more than the rated current In can be fed in. During the voltage dip, as much active power as possible continues to be fed in.
Grid management 4.3 Dynamic grid support Settings Figure 4-37 LVRT & HVRT [3/5] Figure 4-38 LVRT & HVRT [3/5] The function can be set via the following parameters: Parameter number Parameters Range Increment 33135 Current limit for FRT 0 ... 100 % 0.01 % 33129 Entry voltage of LVRT US 0 ... 100 % 0.01 % of the rated voltage Example: A voltage dip of around 10% means 90% remaining grid voltage related to the rated voltage. Continuous operation takes place before this value.
Grid management 4.3 Dynamic grid support 4.3.4 Behavior in the case of voltage rises (low voltage ride through) Due to the growing spread of renewable energy forms, you must ensure that the inverter does not shut down immediately when brief voltage rises occur. The SINVERT PVS inverter has the ability to withstand brief voltage rises and remain on the grid.
Grid management 4.3 Dynamic grid support Settings Note the following points when parameterizing the HVRT curve: ● The parameterized HVRT curve must correspond to the undervoltage protection settings. For this reason, parameterize two of the interpolation points identically to the entered limit values of the overvoltage monitor. See Chapter Voltage monitoring (Page 76). ● When parameterizing, all fields must be filled, but it is not absolutely necessary to use all available interpolation points.
Grid management 4.3 Dynamic grid support The function can be set via the following parameters: Parameter number Parameters Range Increment 32077 HVRT activation On - 33141 HVRT mode Off 32091 HVRT reactive power response • Standard mode • Zero power mode • Q mode • k factor mode • Advanced mode - - 33116 Time t 0 ... 60000 ms 1 ms 33115 Voltage level U / UC 100 ... 200 % 0.
Grid management 4.3 Dynamic grid support 4.3.6 Reactive current provision in the event of voltage rises Function In the event of a voltage rise, the SINVERT PVS inverter can provide reactive current for voltage reduction. The level of the reactive current ΔIB / In additionally fed in when a fault occurs results from the extent of the grid voltage rise ΔU / Un and the k factor. No more than the rated current In can be fed in.
Grid management 4.3 Dynamic grid support Settings Figure 4-43 LVRT & HVRT [5/5] Figure 4-44 LVRT & HVRT [5/5] The function can be set via the following parameters: Parameter number Parameters Range Increment 33135 Current limit for FRT 0 ... 100 % 0.01 % 33131 Entry voltage of HVRT US 100 ... 200 % 0.01 % of the rated voltage Example: A voltage dip of around 10% means 110% remaining grid voltage related to the rated voltage. Continuous operation takes place before this value.
Grid management 4.4 Decoupling protection 4.4 Decoupling protection 4.4.1 Grid monitoring Function The SINVERT PVS inverter monitors the public energy grid for violations of adjustable grid frequency and grid voltage limits. If the limits are violated for an adjustable time, the inverter disconnects from the grid. 4.4.2 Frequency monitoring Function The SINVERT PVS inverter monitors the grid frequency during operation.
Grid management 4.4 Decoupling protection Settings On the "Frequency monitoring" pages, you set the upper and lower limit values (in %) for the grid frequency, as well as the associated delay (in ms). The delay is the minimum time for which a fault must be active to effect shutdown. If the set limit values are undershot or exceeded for the set time, the inverter switches off with an appropriate fault message. Shutdown of the inverter takes approx. 80 ms.
Grid management 4.4 Decoupling protection The function can be set via the following parameters: Parameter number Parameters 32670 Overfrequency moni- 100 ... 150 % toring fH 1 of the rated frequency (50 / 60 Hz) 0.1 % 32672 Overfrequency moni- 100 ... 150 % toring fH 2 of the rated frequency (50 / 60 Hz) 0.1 % 32674 Underfrequency monitoring fH 1 10 ... 100 % 0.1 % Underfrequency monitoring fH 2 10 ... 100 % 32676 4.4.3 Range Increment of the rated frequency (50 / 60 Hz) 0.
Grid management 4.4 Decoupling protection Settings On the "Overvoltage monitoring" and "Undervoltage monitoring" pages, you set the upper and lower limit values (in %) for the voltage, as well as the associated delay (in ms). The delay is the minimum time for which a fault must be active to effect shutdown. If the set limit values are undershot or exceeded for the set time, the inverter switches off with an appropriate fault message. Shutdown of the inverter takes approx. 80 ms.
Grid management 4.4 Decoupling protection The function can be set via the following parameters: Parameter number Parameters Range Increment 32662 Overvoltage monitoriong 1 100 ... 150 % 0.1 % 32664 Overvoltage monitoriong 2 of the rated voltage 100 ... 150 % 0.1 % of the rated voltage 32666 Undervoltage monitoring 1 0 ... 100 % 0.1 % of the rated voltage 32668 Undervoltage monitoring 2 0 ... 100 % 0.1 % of the rated voltage 32663 Tripping delay time tU for overvoltage monitoring 1 0 ..
Grid management 4.4 Decoupling protection 4.4.4 Feed-in conditions In the event of a grid fault, connection of the inverter must be prevented. For this purpose, the SINVERT PVS inverter monitors the grid with regard to frequency and voltage, and switches on if the grid is within a parameterizable range. One limit each is available to you for parameterizing the permissible frequency and voltage range.
Grid management 4.
Application planning 5 The following chapter contains detailed information about packaging, dispatch, delivery, storage, transport, installation location and configuring. Always read and follow the instructions given in this documentation. Observe the relevant safety notices at all times. Make sure that the conditions specified for storage, transport and installation location are fulfilled. 5.
Application planning 5.1 Packaging, dispatch and delivery Design The basic design of the transport pallet is shown in the figure below. This is a customized version of the pallet. ● This is made necessary on the one hand by the dimensions of the cabinet sections ● and on the other hand, this design offers sufficient mechanical stability for safe lifting by a crane.
Application planning 5.1 Packaging, dispatch and delivery 5.1.2 Center of gravity marking and transport position Center of gravity marking The weight mass of the cabinet sections is distributed eccentrically and asymmetrically on both the front and side faces. The weight distribution is indicated directly on each cabinet section of the inverter by the center of gravity marking in accordance with ISO 780/Symbol 7.
Application planning 5.2 Transport 5.1.5 Scope of supply The scope of supply of the SINVERT PVS inverter includes the following: ● Inverter AC cabinet mounted on transport pallet ● Inverter DC cabinet mounted on transport pallet ● Accessories pack (on Euro pallet): – 1 x cable 4 m fitted with lugs at both ends, on pallet – 1 x mounting kit for screwing the cabinet sections in black crate – Hexagonal screw M12x50, strain washer, hexagonal nut ● Operating instructions (compact) as hard copy 5.
Application planning 5.2 Transport Mechanical connection between pallet and inverter cabinet section ● Never transport the pallet with the inverter cabinet section without a secure mechanical connection between the pallet and inverter. See the figure below. ● The mechanical connection comprises strapping and bolting of cabinet base to the pallet. ● Before the package is moved, the bolting and strapping must be checked to ensure they are secure.
Application planning 5.2 Transport Danger of tipping of the transportation unit WARNING Danger to life from tipping! A cabinet, whether with or without pallet, must never be tipped in any direction. The cabinet is very heavy. Tipping it too far and causing it to topple over can therefore result in serious injury, death and substantial property damage.
Application planning 5.2 Transport Mechanical connection between the inverters The SINVERT inverter is transported in two consignment units or cabinet sections. No provision is made for transporting connected cabinet sections. Figure 5-5 Impermissible transport of two cabinet sections The inverter cabinet sections must never be transported once they have been assembled into a single unit.
Application planning 5.2 Transport 5.2.2 Transporting using pallet truck and fork-lift truck The operator of the pallet truck must always ensure that the equipment required to move the load is in good working order and that high standards of operational safety are fulfilled. Loads must always be transported in compliance with all relevant health and safety regulations as well as the instructions in this documentation.
Application planning 5.2 Transport 5.2.3 Transporting by crane 5.2.3.1 General notices The crane driver must always ensure that the crane and the equipment required to move the load are in good working order and that high standards of operational safety are fulfilled. Loads must always be transported in compliance with all relevant health and safety regulations as well as the instructions in this documentation.
Application planning 5.2 Transport 5.2.3.2 Permissible transport methods There are basically two permissible methods of transporting the cabinets by crane: ● Transport with H beam ● Transport with frame structure The cabinets are not designed to be transported by any other method and other methods are not therefore permitted. If you choose a method of crane transport which is not expressly approved in this document, Siemens will not accept liability for the consequential damage.
Application planning 5.2 Transport Procedure Whether a load is transported by crane on an H beam or a specially designed frame structure, it is always essential that the inverter is mechanically coupled to the pallet. 1. The crane ropes are placed under the load at a marked position in parallel to the side wall. 2. They are then brought up in parallel to and at an appropriate distance from the straps, from where they are threaded through a frame structure or attached to the H beam.
Application planning 5.2 Transport 5.2.3.
Application planning 5.2 Transport 5.2.4 Transport and alignment of cabinets in electrical operating areas Removing the transport locks The cabinets are attached to the pallet by means of transport locks (upward-facing screws). 1. To lift the cabinets off the pallet, you first need to undo the screw nuts. 2. To slide the cabinets off the pallet, you need to push the screws out downwards far enough (e.g. using a hammer and a thick nail), so that the surface of the pallet becomes smooth.
Application planning 5.2 Transport Procedure 1. Adjust the pallet so that it is level with the adjacent surface, e.g. floor of the equipment room. 2. Cover the gap between the pallet and floor with a metal sheet (5 to 10 cm) so that the rollers do not get caught in the gap. 3. Place a roller on the metal sheet and under the cabinet frame. 4. Place a thick roller under the cabinet at a position where there are no cross-planks in the pallet. 5.
Application planning 5.3 Storage 5.3 Storage It is absolutely essential that the inverter units are stored in compliance with the storage conditions as described in Chapter Environmental conditions (Page 185).
Application planning 5.4 Site of installation 5.4 Site of installation The site of installation must comply with certain requirements relating to environmental conditions, construction and layout of operating areas, connections to be provided, noise control, fire protection, EMC and ventilation. Detailed information about the requirements of the installation site can be found below. 5.4.
Application planning 5.4 Site of installation 5.4.2 Requirements of electrical operating areas In addition to the environmental conditions for operation and the general requirements of sites of installation, electrical operating areas must also comply with further special requirements. The SINVERT inverter must be installed in a locked electrical operating area.
Application planning 5.
Application planning 5.4 Site of installation 5.4.
Application planning 5.5 Configuring information 5.5 Configuring information Note the following points when configuring the PV plant. Permissible DC currents When dimensioning the PV plant, ensure that the DC currents do not exceed the permissible DC current in any state. Specification of the medium-voltage transformer and additional overvoltage protection elements Each subunit of the inverter must be connected to the medium-voltage transformer with galvanic isolation.
Installation 6.1 6 Preparation This chapter contains instructions and tips on the correct installation of the SINVERT PVS 600Series. Always take note of the safety notices in the relevant chapters. Always comply with the relevant local rules and regulations which apply at the site of installation. General Information The devices must be installed and cooled in accordance with the guidelines in this document. Protect the inverters against impermissible loads.
Installation 6.2 Safety information on bolting the cabinet sections together 6.2 Safety information on bolting the cabinet sections together NOTICE Mechanical damage Stresses occurring during transport can exert mechanical pressure on the components. This can result in property damage. • Line the cabinets up precisely with each other in order to avoid shearing forces when the base units are bolted together.
Installation 6.3 Bolting the cabinet sections together 6.3 Bolting the cabinet sections together Proceed as follows to bolt the cabinet sections together: 1. Remove the following covers: – The cover of the AC capacitors – The inverter covers – The protective grilles on the two cabinet sections 2. Place the cabinets together in such a way that the side panels with their fixing holes are coincident. 3.
Installation 6.4 Mechanical connection to the foundation 6.4 Mechanical connection to the foundation There are holes in the frame of the cabinets which allow them to be bolted to the floor. Alternatively, when mounting the cabinets to steel beams it is possible for to the cabinets to be welded to the base. When fixing the cabinets to the base, the procedure used and the type of attachment should be adapted to the conditions of each installation.
Installation 6.5 Installing the exhaust-air shrouds (optional) 6.5 Installing the exhaust-air shrouds (optional) The exhaust-air shrouds are available as accessories. For details, see Section Accessories (Page 208). The exhaust-air shrouds for the AC cabinet and the DC cabinet of the inverter differ only in their air deflectors. The basic shroud, partition, and cross struts are identical on both exhaust-air shrouds.
Installation 6.5 Installing the exhaust-air shrouds (optional) In the case of the AC cabinet, the supplied foam rubber must also be applied after installation of the exhaust-air shroud to guarantee the desired air flow. Figure 6-3 Exhaust-air shrouds: Fitting the foam rubber 1. Open the door of the AC cabinet to gain access to the underside of the installed exhaustair shroud. 2.
7 Connecting 7.1 Universal safety instructions For the sake of your own personal safety and to avoid the risk of property damage, follow the safety notices below. Pay particular attention to the safety notes on the actual product and read the documentation and the safety information for all the devices of the system. DANGER Danger due to high voltages High voltages cause death or serious injury if safety instructions and notices are not observed or if the equipment is handled incorrectly.
Connecting 7.
Connecting 7.2 Cabling 7.2 Cabling Use only the cables listed in the tables below. Table 7- 1 External cable connections: Power supply Grounding Cable type Current carrying capacity Screw type At least 240 mm2 750 A M12 3 phases with 16 A each Terminal block mm2 AC auxiliary power supply 5 x 1.
Connecting 7.3 Connecting the individual cables 7.3 Connecting the individual cables 7.3.1 Requirements This chapter contains information and instructions on how to connect all signal cables and power cables as required prior to initial commissioning. Requirements The following requirements must be met prior to starting the individual connection tasks: ● All DC and AC infeed cables to all inverter subunits must be isolated.
Connecting 7.
Connecting 7.3 Connecting the individual cables Torques for current-carrying screw connections The following torques apply for tightening the current-carrying screw-type connections: Table 7- 3 7.3.3 Torques for current-carrying screw connections Screw Torque AC outputs 70 Nm DC inputs 70 Nm Grounding 70 Nm Grounding 1. Connect every cabinet to ground potential at the grounding lug (see figure in Chapter Overview (Page 110)) using an appropriate cable.
Connecting 7.3 Connecting the individual cables 7.3.4 Signal cables and internal communication Signal cables Figure 7-2 Communication terminal compartment 1. Insert the signal cables with the connectors X1 and X2 into the X1 and X2 sockets provided for this on the left frame of the AC cabinet. 2.
Connecting 7.3 Connecting the individual cables Profibus connection in the case of master/slave combinations In the case of master/slave combinations, establish the Profibus connection between the master and the slaves using the specified cables (see Chapter Cabling (Page 109)). Note Terminating resistors You must note the following in the case of the first and last PROFIBUS nodes: (The first PROFIBUS node is always the ET200S of the master. The last PROFIBUS node is the PAC 4200 in the last slave.
Connecting 7.3 Connecting the individual cables Connection on the master Figure 7-3 Running the Profibus cable in the master 1. Run the Profibus cable into the bottom of the AC cabinet and then up and through the hole in the partition to the PAC 4200 as shown in the drawing. 2. Connect it to the PAC 4200 (-A200). – To do so, open the connector (6GK1500-0FC10) and connect the red and green core of the cable to the contacts with the same core colors. 3.
Connecting 7.3 Connecting the individual cables Connection on the slave Figure 7-4 Running the Profibus cable in the slave 1. Insert the cable into the DC cabinet from bottom left, and run it up the frame as shown in the drawing. 2. Connect it to the ET200S (-A1 -IM). – To do so, open the relevant connector and connect the red and green cores of the cable to the contacts with the same core colors. 3. Connect the shield of the Profibus cable to the shield terminals in the DC cabinet. 4.
Connecting 7.3 Connecting the individual cables Connection on the slave if there is no option available If none of the following options is available ● D30/D40 PV: Field grounding, ● D61: Max. DC voltage 1000 V, ● M10: Symmetry monitoring, there is no ET200 in the DC cabinet and the Profibus cable must be connected in the slave to the module CU320 (see figure "Running the Profibus cable in the slave"). 1. Connect the Profibus cable to the CU320 (-A201).
Connecting 7.3 Connecting the individual cables 7.3.5 Connection for the option "PV array grounding" In the case of the PV array grounding option, the relevant cable connections must be established between the master and the slave cabinets. The connecting cable is located in the slave and is already connected there. It only has to be run to the master and connected.
Connecting 7.3 Connecting the individual cables 7.3.6 External communication To establish communication with the "outside", a connection to the Internet is established via a router. For this purpose, connect the relevant cable with the associated connection of the SCALANCE module -A202 in the AC cabinet. Figure 7-6 Innenansicht_Kommunktion 1.
Connecting 7.3 Connecting the individual cables 7.3.7 Figure 7-7 Connection between DC and AC cabinet Making the connection between the DC and AC cabinet 1. Remove the cover at bottom-right of the DC cabinet. 2. Remove the fan unit at bottom-left of the AC cabinet. 3. Take the longest double cable L3 from the area under the inverter power supply unit and run it through the side opening on the right into the AC cabinet. 4.
Connecting 7.3 Connecting the individual cables 7.3.8 AC auxiliary power supply The inverters are supplied with an auxiliary voltage of 400 V. Figure 7-8 Connection of AC auxiliary power supply 1. Run the 3-phase cable for the AC auxiliary power supply as shown in the figure, and connect the three phases (L1,L2,L3,N, PE) to the terminal block –X240 (see Appendix Overview of master slave cabling (Page 211)). 2.
Connecting 7.3 Connecting the individual cables 7.3.9 Main AC grid Figure 7-9 AC connection 1. Connect the AC power cable to the terminals L1, L2 and L3. 2. Tighten the screw connections of the AC connection with a torque of 70 Nm. 3. Secure the AC power cable to the cable clamping strip to guarantee strain relief. Note Connection at the medium-voltage transformer Each subunit of the inverter must be connected to the medium-voltage transformer with galvanic isolation.
Connecting 7.3 Connecting the individual cables 7.3.10 DC link (only for master-slave combinations) This connection must only be made in the case of master/slave combinations. Figure 7-10 DC link connection Ensure that the DC link is free of voltage. 1. Connect the DC link power cables to the copper bars marked "L+" and "L-" an. – Copper bar "L+" is at the front and "L-" behind it – The DC link cables are double cables.
Connecting 7.3 Connecting the individual cables 7.3.11 DC input Figure 7-11 DC connection 1. Ensure that the DC power cable is isolated on the PV side. – For this purpose, the PV field must be isolated by a switch disconnector or at the combiner box. 2. Connect the DC power cables to the terminals 1L, 2L and 3L. – The DC power cables are double cables. For this reason, one cable must be applied to the terminal bar at the front and the other behind. – It is essential to ensure correct polarity. 3.
Connecting 7.4 Rapid stop function 7.4 Rapid stop function The "rapid stop function" is used for fast shutdown of the AC grid in the event of faults. Installation of a corresponding external switch with this function is therefore absolutely necessary. WARNING Without the rapid stop function, shutdown of the AC grid in the event of faults is not possible. If no rapid stop function is installed, the inverter subunit cannot be separately isolated.
Connecting 7.4 Rapid stop function Requirements for switch and cable ● Switch (NC) designed for 16 A DC ● Shielded cable 2 x 2.5mm2 Procedure for installation and connecting 1. Install the rapid stop switch at a suitable, easily accessible point close to the cabinet. The distance to the cabinet must be less than 10 m. 2. Lay a 2-core shielded cable (2.5mm2) and connect it to the rapid stop switch. 3. Remove the jumper between the terminals X20 -1/-2 in the AC cabinet. 4.
Commissioning 8.1 8 Overview Commissioning of the PVS inverter must be carried out by qualified Siemens personnel. The following steps must be carried out for commissioning: On the master 1. Connect the AC auxiliary power supply 2. Connect AC voltages to the connecting cable and check phase sequence 3. Connect DC voltages to the connecting cable and check polarity 4.
Commissioning 8.2 Commissioning the inverter 8.2 Commissioning the inverter The procedure described below applies for the complete inverter unit. We recommend that you commission the inverter "master" subunit first and then the slave subunits. Requirements ● The cabinet has been installed correctly. ● The cabinet has been connected up correctly. ● The rapid stop switch is installed. ● The green "READY" indicator light in the control cabinet door does not light up. Procedure for master 1.
Commissioning 8.2 Commissioning the inverter 8. Check the polarity of the DC voltage with a suitable measuring device (e.g. multimeter) – If the polarity is incorrect, the corresponding power cables have to be swapped in the connection area of the DC input (see Chapter DC input (Page 124)). 9. Turn the key-operated switch in the AC cabinet door to the position "2-Enable".
Commissioning 8.2 Commissioning the inverter Language selection After switching on the power supply, the screen for language selection is the first to appear on the touch panel of the master. (For more information on operating the touch panel, see also Chapter Operating and monitoring the inverter via the touch panel (Page 141)) 1. Select the desired language and confirm with OK.
Commissioning 8.2 Commissioning the inverter Set the system time Proceed as follows to set the system time: 1. In the start window, touch the "Main Menu" button in the upper area of the touch screen. The main menu is displayed: 2. Touch the "Settings" button. The "SINVERT - Settings" menu is displayed: 3. Touch the "Time Setting" button. The screen form for entering the system time is displayed.
Commissioning 8.2 Commissioning the inverter 4. Touch the field "Desired System Time" and enter the desired date and time-of-day with the numerical keypad. – Use the arrow keys to change the cursor position within the line. – Use the "BSP" button to delete one character at a time at the cursor position. – Use the the "ESC" button to exit the window without changes. – Use the "Return" button to confirm the input and exit the window.
Commissioning 8.3 Parameterizing the inverter 8.3 Parameterizing the inverter Adapt inverter to system requirements Depending on the application, it is necessary to adapt the inverter to specific system requirements by modifying parameters. You can find the available setting parameters in Chapter Operator control and monitoring (Page 137). The parameters of the inverter have pre-assigned values. These values must be checked during commissioning and adapted if necessary.
Commissioning 8.4 Decommissioning the inverter 8.4 Decommissioning the inverter 8.4.1 Decommissioning an inverter subunit With the SINVERT PVS, an inverter subunit can be decommissioned individually. This means that if an error occurs in one inverter subunit, the other inverter subunits can remain in operation. Procedure 1. Turn the key-operated switch in the AC cabinet door of the inverter subunit to be switched off to the position "1-Lock".
Commissioning 8.4 Decommissioning the inverter Procedure 1. Turn the key-operated switch in the AC cabinet door on all inverter subunits to the position "1-Lock". – After the first subunit is switched off, the complete inverter shuts down and attempts to switch on again after 30 s in a controlled fashion, apart from the inverter subunits on which the key-operated switch is already in the "1-Lock" position.
Commissioning 8.
Operator control and monitoring 9 Only qualified personnel may operate the inverter. 9.
Operator control and monitoring 9.2 Parameters 9.2 Parameters The inverter functions are adapted to the specific plant requirements using parameters. These parameters are stored in the software of the SINVERT PVS inverter. ● A unique number is assigned to each parameter. ● A large number of parameters can be accessed via the touch panel. ● Some parameters are only accessible for communication via the Ethernet interface.
Operator control and monitoring 9.3 Controlling the inverter via the operator panel 9.3 Controlling the inverter via the operator panel Design of the operator and display panel The operator and display panel of the SINVERT PVS inverter unit in the AC cabinet door of the master is designed as shown below.
Operator control and monitoring 9.3 Controlling the inverter via the operator panel Control and display elements You can enable and disable an inverter subunit via the key-operated switch in the control cabinet door. The display elements also indicate the status of the inverter subunit.
Operator control and monitoring 9.4 Operating and monitoring the inverter via the touch panel 9.4 Operating and monitoring the inverter via the touch panel 9.4.1 Introduction You can enter all operating commands for the inverter via the touch panel in the cabinet door. Furthermore, you can parameterize the SINVERT PVS inverter via the touch panel and check the inverter data. The touch panel features intuitive menu prompting for this purpose. 9.4.
Operator control and monitoring 9.4 Operating and monitoring the inverter via the touch panel 9.4.3 Start window (status indicator) After switching on the power supply, a language must first be selected. Then, the start window will appear with the status indicator.
Operator control and monitoring 9.4 Operating and monitoring the inverter via the touch panel Operating status display The operating status of the inverter and the individual inverter subunits is indicated by the color in the corresponding box. The meaning of the colors is shown in the table below. Color 9.4.4 Meaning Inverter (INV) Inverter subunit (INSU 1/INSU 2 ...) Blue All inverter subunits are off.
Operator control and monitoring 9.4 Operating and monitoring the inverter via the touch panel Access level and password Some of the submenus and parameter changes are password-protected. This prevents unauthorized or inadvertent changing of device parameters. The Service menu is reserved for service personnel. The following access levels are available to you: Access level Password Authorization Guest without password Read only access to parameters.
Operator control and monitoring 9.4 Operating and monitoring the inverter via the touch panel 9.4.5 General information on working with the tool The touch panel can be operated using the buttons in the individual windows. In addition, the following instructions must be observed: ● Each touch panel window contains a "Back" button via which you can return to the nexthigher level. ● If a menu item has more than one window, you can scroll up and down using additional buttons.
Operator control and monitoring 9.5 Parameter list 9.5 Parameter list 9.5.1 Introduction The lists below contain all the parameters that can be changed on the Service pages. See also SINVERT support (http://www.siemens.
Operator control and monitoring 9.5 Parameter list 9.5.2 DC settings Designation Default Min Max Description Min. switch-on voltage 600 V 600 V 1000 V Minimum voltage for switching on the inverter Max. switch-on voltage 1000 V 600 V 1000 V Maximum voltage for switching on the inverter Min. voltage for switching in the contactors 500 V 500 V 500 V Min. voltage for switching in the DC contactors Max. voltage for switching in the contactors 1000 V 1000 V 1000 V Max.
Operator control and monitoring 9.5 Parameter list 9.5.3 Grid parameters Designation Default Min Max Overvoltage delay 1 100 ms 0 5 000 ms Overvoltage delay 2 0 ms 0 5 000 ms Undervoltage delay 1 1 500 ms 0 5 000 ms Undervoltage delay 2 300 ms 0 5 000 ms Overvoltage limit value 1 115.00 % 100 % 150 % Overvoltage limit value 2 125.00 % 100 % 150 % Undervoltage limit value 1 80.00 % 10 % 100 % Undervoltage limit value 2 45.
Operator control and monitoring 9.5 Parameter list 9.5.4 Temperatures and times Note In the case of changes, all times must be entered in ms using the numeric keypad.
Operator control and monitoring 9.
Operator control and monitoring 9.5 Parameter list 9.5.5 Miscellaneous Designation Default Min Max Additional setpoint DC voltage 100 V -200 V 150 V Additional setpoint reactive power 0 var 0 var 0 var Setpoint current limit ALM -960 A -1000 A -1 A Number of fan modules 1 1 50 Voltage divider factor (1000 V resistance) 1.429 0 5 Number of inverters in the inverter unit 1 1 4 DC contactors per inverter 3 3 3 Number of ISO DC contactor checks per day 3 0 5 Min.
Operator control and monitoring 9.6 Rapid stop function 9.6 Rapid stop function The "rapid stop function" of the PVS inverter unit is used for fast shutdown of the AC grid in the event of faults and emergencies (e.g.: component malfunctions, excessively high temperatures, etc.). Triggering the rapid stop function results in infeed mode abort. WARNING Hazardous voltages in the cabinet following actuation of rapid stop The system is not isolated even after actuation of the rapid stop function.
10 Fault, alarm and system messages 10.1 Fault messages Display of the fault messages Fault messages comprising the following data are displayed on the touch panel: ● Time at which fault occurred ● Fault text ● Fault number ● Fault value ● Fault status Fault messages of the inverter unit The following table shows the faults of the inverter unit that are reported on the touch panel.
Fault, alarm and system messages 10.1 Fault messages Fault messages of the inverter subunit The following table shows the faults of the inverter subunit that are reported on the touch panel.
Fault, alarm and system messages 10.2 Fault correction 10.2 Fault correction Fault messages for the inverter unit In this section, you will find all fault messages for the inverter unit and their descriptions, possible causes and possible corrective measures. This data is made available in the form of a table for each fault message: Fault number 1 – RapidStop – Rapid Stop triggered Description Control Unit records a request for rapid stop of the inverter.
Fault, alarm and system messages 10.2 Fault correction Fault number 24 – Plausibility Check – Grounding Current > Grounding Current Max Description Control Unit records an excessively high grounding current. Possible causes Incorrect connection of the current transducer for measuring the grounding current Measures Check the wiring of the current transducer for measuring the grounding current.
Fault, alarm and system messages 10.2 Fault correction Fault number 51 – Fault Ride Through - Low Voltage Ride Through times error Description The Control Unit has detected that the times of the LVRT configuration have been set incorrectly.
Fault, alarm and system messages 10.2 Fault correction Fault messages for the inverter subunit In this section, you will find all fault messages for the inverter subunit and their descriptions, possible causes and possible corrective measures. This data is made available in the form of a table for each fault message: Fault number 11 - Grid Monitoring - Line to Neutral low voltage trip Description Control Unit records an excessively low phase-to-neutral voltage (P2N) at the AC output of the inverter.
Fault, alarm and system messages 10.2 Fault correction Fault number 14 - Grid Monitoring - Line to Line high voltage trip Description Control Unit records an excessively high phase-phase voltage at the AC output of the inverter. Possible causes System overvoltage on at least one of the system phases Measures If necessary, adapt the parameter settings.
Fault, alarm and system messages 10.2 Fault correction Fault number 18 - Grid Monitoring - Line to Line high filter voltage trip Description Control Unit records an excessively high phase-phase voltage at the AC output filter of the inverter. Possible causes • System overvoltage on at least one of the system phases • Incorrect parameter settings Measures If necessary, adapt the parameter settings.
Fault, alarm and system messages 10.2 Fault correction Fault number 32 – Peripheral Faults – Reactor Temperature Fault Description Control Unit records a temperature fault of the reactor (T ≥ 180 °C). Possible causes • Wire break of the overtemperature signal • Reactor fans defective • Ventilation inlet of the reactor covered Measures Proceed depending on the fault cause • Replace the broken wire if there is a wire break and acknowledge the fault. • Replace the reactor fans.
Fault, alarm and system messages 10.2 Fault correction Fault number 41 – Plausibility Check – DC Link Current < DC Link Current Min Description Control Unit records an excessively low DC link current. Possible causes Short-circuit in the PV field Measures Check for a short-circuit in the PV field Fault number 42 – Plausibility Check – DC Link Current > DC Link Current Max Description Control Unit records an excessively high DC link current.
Fault, alarm and system messages 10.2 Fault correction Fault number 47 – Plausibility Check – Supply Air Temp < Supply Air Temp Min Description Control Unit records an excessively low supply air temperature. Possible causes • Incorrect connection of the temperature sensor for the supply air temperature of the inverter • Supply air temperature outside tolerance Measures Check the wiring of the temperature sensor for measuring the supply air temperature.
Fault, alarm and system messages 10.2 Fault correction Fault number 52 – Plausibility Check – DC Voltage Input x > DC Voltage InputMax Description Control Unit records an excessively high DC input voltage at an input. Possible causes • Incorrect PV field configuration • Incorrect connection of the option DC input voltage measurement Measures Proceed depending on the fault cause: • Check the interconnection of the PV modules and strings. • Check the wiring of the DC input voltage measurement.
Fault, alarm and system messages 10.2 Fault correction Fault number 64 – Feedback Monitoring – DC precharge resistor contactor 3 Description Control Unit records a checkback signal fault of DC precharge resistor contactor 3. Possible causes • The contacts of the contactor are stuck • The coil of the contactor is defective • Wire break on the cable for the checkback signal of the contactor • Check the contactor for a defect. • Check the wiring of the checkback signal of the contactor.
Fault, alarm and system messages 10.3 Alarms 10.3 Alarms Display of the alarms Alarms comprising the following data are displayed on the touch panel: ● Time at which alarm occurred ● Alarm text ● Alarm status Inverter unit alarm messages The following table shows the alarms of the inverter unit that are reported on the touch panel.
Fault, alarm and system messages 10.4 Correction of the alarms 10.4 Correction of the alarms Alarm messages for the inverter unit In this section, you will find all alarms for the inverter unit and their descriptions, possible causes and possible corrective measures. This data is made available in the form of a table for each alarm message: Alarm number 11 - Isolation Routine - Isolation warning detected Description The isolation of the PV modules with respect to ground is lower than the 1st limit.
Fault, alarm and system messages 10.4 Correction of the alarms Alarm messages for the inverter subunit In this section, you will find all alarm messages for the inverter subunit and their descriptions, possible causes and possible corrective measures. This data is made available in the form of a table for each alarm message: Alarm number 1 - Surge Protection - Change the surge protection AC side Description The overvoltage protection on the AC side has tripped.
Fault, alarm and system messages 10.4 Correction of the alarms Alarm number 31 / 32 / 33- DC Contactor - DC Contactor 1 / 2 / 3 feedback fault Description The DC contactor does not provide any feedback. Possible causes • DC contactor of the inverter subunit 1, 2 or 3 is defective • Broken cable Measures Check the DC contactor for possible faults.
Fault, alarm and system messages 10.5 Event messages 10.5 Event messages Displaying event messages Event messages comprising the following data are displayed on the touch panel: ● Event time (date and time) ● Event text Up to 20 event messages can be tracked on the touch panel (storage of 35 event messages). Event messages of the inverter unit The following table shows the event messages of the inverter unit that are reported on the touch panel.
Fault, alarm and system messages 10.5 Event messages Event messages of the inverter subunit The following table shows the event messages of the inverter subunit that are reported on the touch panel.
Fault, alarm and system messages 10.5 Event messages Event description for the inverter unit In this section, you will find all event messages for the inverter unit and their descriptions. This data is made available in the form of a table for each event message: Event number 1 – MPP Tracker – MPPT--MPP tracker stopped Event MPPT – MPP tracker stopped Description MPP tracking was used.
Fault, alarm and system messages 10.5 Event messages Event number 21 – Fault Manager – No faults in system Event No faults in the system Description The inverter unit was operating at the ideal level and fault-free. Event number 22 – Fault Manager – Fault detected--Automatic reset Event Fault detected – Automatic reset Description The Fault Manager detected a fault in the inverter unit that results in an automatic acknowledgment.
Fault, alarm and system messages 10.5 Event messages Event description for the inverter subunit In this section, you will find all event messages for the inverter subunit and their descriptions. This data is made available in the form of a table individually for each event message. Event number 1 – Mini Panel – Key switch activated Event Keyswitch activated Description The keyswitch of the inverter unit has been activated and the device has thus been started up.
Fault, alarm and system messages 10.5 Event messages Event number 21 – Contactors – DC contactor 1 closed Event DC contactor 1 closed Description DC contactor 1 has been closed. The first DC input of the inverter subunit has been started up. Event number 22 – Contactors – DC contactor 1 opened Event DC contactor 1 opened Description DC contactor 1 has been opened. The first DC input of the inverter subunit has been switched off.
Fault, alarm and system messages 10.5 Event messages Event number 28 – Contactors – DC precharge contactor 1 opened Event DC precharge contactor 1 opened Description DC precharge contactor 1 has been opened. Event number 29 – Contactors – DC precharge contactor 2 closed Event DC precharge contactor 2 closed Description DC precharge contactor 2 has been closed. Event number 30 – Contactors – DC precharge contactor 2 opened Event DC precharge contactor 2 opened.
Fault, alarm and system messages 10.5 Event messages Event number 36 – Contactors – DC precharge contactor Rp opened Event DC precharge contactor Rp opened Description DC precharge contactor Rp has been opened. Event number 41 – Fans – Fans grade 1 activated Event Fans grade 1 activated Description Fans grade 1 have been activated. Event number 42 – Fans – Fans grade 1 deactivated Event Fans grade 1 deactivated Description Fans grade 1 have been deactivated.
Fault, alarm and system messages 10.6 Messages of the operator panel 10.6 Messages of the operator panel The indicator lights on the operator panel in the cabinet door signal the following information: Table 10- 7 Information signaled by the operator panel indicator lights Operator control State Description Green indicator light Not illuminated 1. Check the grid voltage. "Run" 2. Please contact Technical Support. Flashing slowly, 1 s cycle Move the key-operated switch to position "2".
11 Maintenance 11.1 Servicing The term "servicing" refers to any measure which restores the control cabinet to a fully functional operating state. Replaceable components You are allowed to replace the following components. ● Fuses ● Overvoltage arresters ● Reactor fans ● Inverter fans 11.2 Maintenance The term "maintenance" refers to any measure which maintains the control cabinet in a fully functional operating state.
Maintenance 11.3 Cleaning the inside of the cabinet 11.3 Cleaning the inside of the cabinet Requirements ● The inverter has been properly shut down. See Chapter Decommissioning the entire inverter (Page 134). ● A voltage tester is available to check that the cabinet is de-energized. ● A cabinet key is available. ● Cleaning brush and vacuum cleaner are available. ● A supply of oil-free compressed air up to maximum 1 bar is available. Clean the cabinet 1. Check that the cabinet is de-energized. 2.
Maintenance 11.4 Replacing the reactor fan 11.4 Replacing the reactor fan Requirements ● The control cabinet has been properly shut down. See Chapter Decommissioning the entire inverter (Page 134). ● The feeders at the DC and AC inputs are de-energized. ● A voltage tester is available to check that the cabinet is de-energized. ● A cabinet key is available. Procedure 1. Open the cabinet doors. 2. Check that the cabinet is de-energized. 3. Disassemble the fan plates and unplug the connector at the fans 4.
Maintenance 11.
Maintenance 11.5 Replacing the fan of the inverter module (ALM) Removal steps 1. Open the control cabinet doors. 2. Check safe isolation from power supply. 3. Remove the protective cover from the inverter module. 4. Unscrew 8 screws and remove the busbar – The removal steps are numbered in accordance with the figure. 5. Remove the retaining screws for the fan (3 screws) 6. Disconnect the supply cables to the fan (1 x "L", 1 x "N") 7.
Maintenance 11.
12 Technical data 12.1 Environmental conditions Storage and transport Ambient temperature -25 °C ... +70 °C Relative humidity 0 % ... 95 % Operation Ambient temperature 0°C ... 50°C Relative humidity/without condensation 0 % ...
Technical data 12.2 Mechanical data 12.2 Mechanical data Date Specification Mounting position vertical Type of fixing Floor mounting Dimensions without pallet (W x H x D) Per control cabinet Both control cabinets (mounted) together 2 700 x 2 100 x 730 mm Weight Overall system1) PVS 600Series 2 085 kg Pallet/per cabinet approx.
Technical data 12.3 Electrical data 12.3 Electrical data Input data (DC) PVS500 PVS500 PVS1000 PVS1500 MPP voltage range PVS2000 450 ... 750 V Maximum input voltage 820 V (1 000 V optional) Minimum input voltage 450 V Rated input voltage 465 VDC Rated input power 513 kW 1 026 kW 1 539 kW 2 052 kW Maximum input current 1 103 A 2 206 A 3 309 A 4 412 A Number of DC inputs 3 6 9 12 Maximum current per input 368 A Maximum current of the master/slave connection.
Technical data 12.3 Electrical data Efficiency/power losses PVS500 PVS500 PVS1000 PVS1500 PVS2000 European efficiency1) 98.1 % 98.3 % 98.3 % 98.3 % CEC efficiency1) 98.2 % 98.3 % 98.3 % 98.3 % Maximum efficiency1) 98.
Technical data 12.3 Electrical data Input data (DC) PVS585 PVS585 PVS1170 PVS1755 MPP voltage range PVS2340 530 ... 750 V Maximum input voltage 820 V (1 000 V optional) Minimum input voltage 530 V Rated input voltage 540 VDC Rated input power 598 kW 1 196 kW 1 794 kW 2 392 kW Maximum input current 1 104 A 2 208 A 3 312 A 4 416 A Number of DC inputs 3 6 9 12 Maximum current per input 368 A Maximum current of the master/slave connection.
Technical data 12.3 Electrical data Efficiency/power losses PVS585 PVS585 PVS1170 PVS1755 PVS2340 European efficiency1) 98.2 % 98.4 % 98.4 % 98.4 % CEC efficiency1) 98.3 % 98.3 % 98.4 % 98.4 % Maximum efficiency1) 98.
Technical data 12.3 Electrical data Input data (DC) PVS600 PVS600 PVS1200 PVS1800 MPP voltage range PVS2400 570 ... 750 V Maximum input voltage 820 V (1 000 V optional) Minimum input voltage 570 V Rated input voltage 570 VDC Rated input power 613 kW 1 226 kW 1 839 kW 2 452 kW Maximum input current 1104 2 208 A 3 312 A 4 416 A Number of DC inputs 3 6 9 12 Maximum current per input 368 A Maximum current of the master/slave connection.
Technical data 12.3 Electrical data Efficiency/power losses PVS600 PVS600 PVS1200 PVS1800 PVS2400 European efficiency1) 98.4 % 98.6 % 98.6 % 98.6 % CEC efficiency1) 98.5 % 98.6 % 98.6 % 98.6 % Maximum efficiency1) 98.
Technical data 12.3 Electrical data Input data (DC) PVS630 PVS630 PVS1260 MPP voltage range PVS1890 PVS2520 570 ... 750 V Maximum input voltage 820 V (1 000 V optional) Minimum input voltage 570 V Rated input voltage 600 VDC Rated input power 643 kW 1 286 kW 1 929 kW 2 572 kW Maximum input current 1 104 A 2 208 A 3 312 A 4 416 A Number of DC inputs 3 6 9 12 Maximum current per input 368 A Maximum current of the master/slave connection.
Technical data 12.3 Electrical data Efficiency/power losses PVS630 PVS630 PVS1260 PVS1890 PVS2520 European efficiency1) 98.3 % 98.5 % 98.5 % 98.5 % CEC efficiency1) 98.4 % 98.5 % 98.5 % 98.5 % Maximum efficiency1) 98.
Technical data 12.3 Electrical data General electrical data Power components IGBT Galvanic isolation AC side AC output direct at medium voltage transformer Each subunit of an inverter must be connected to the medium-voltage transformer with galvanic isolation. Auxiliary power supply per inverter 400 V ± 10%, 50 Hz / 60 Hz; (47 ...
Technical data 12.
Technical data 12.
Technical data 12.4 Operator panel and interfaces 12.4 Operator panel and interfaces Display Data interface 12.
Dimension drawings 13.
Dimension drawings 13.
Dimension drawings 13.2 Base plate 13.
Dimension drawings 13.3 Exhaust-air shrouds (optional) 13.3 Exhaust-air shrouds (optional) The exhaust-air shrouds are available as accessories. For details, see Section Accessories (Page 208). The exhaust-air shrouds for the DC cabinet and the AC cabinet of the inverter differ only in their air deflectors. The basic shroud, partition, and cross struts are identical on both exhaust-air shrouds.
Dimension drawings 13.
Dimension drawings 13.
14 Ordering data 14.
Ordering data 14.
Ordering data 14.2 Options 14.
Ordering data 14.3 Accessories 14.3 Accessories Exhaust-air shroud You can find information about the available accessories in the current catalog, obtainable from your sales partner.
Technical support A Technical support for SINVERT products ● Contacts, information material and downloads for SINVERT products: SINVERT Product page (http://www.siemens.com/sinvert) Here you can find, for example: – Catalogs – Brochures ● Documentation on SINVERT products: SINVERT support (http://www.siemens.
Technical support PVS 600Series 210 Operating Instructions, 08/2014, A5E03467293-003
Overview of master slave cabling B Overview of master slave cabling Figure B-1 Overview of master slave cabling PVS 600Series Operating Instructions, 08/2014, A5E03467293-003 211
Overview of master slave cabling PVS 600Series 212 Operating Instructions, 08/2014, A5E03467293-003
Index A F Accessories, 208 Active power control, 38 According to frequency P(f), 40 During the switch-on operation, 46 Fixed setpoint, 39 Air extraction, 99 Air supply, 99 Alarms, 166 Fault messages, 153 Feed-in conditions, 79 Foundation, 96 Frequency monitoring, 74 C Cabinet heating, 31 Cleaning Inside of cabinet, 180 Commissioning, 128 Communication, 37 Conformity, 198 Control cabinet Dimension drawing, 199 D Decoupling protection, 36, 74 Delivery, 83, 83 Dimension drawings Control cabinet, 199 Exhau
Index L LVRT curve, 64 M Maintenance, 179 Master/slave operation, 21 Mechanical data, 186 Mechanical installation, 101 Messages of the operator panel, 178 O Operation Touch panel, 141 Operator controls, 139, 140 Operator panel Messages, 178 Technical data, 198 Ordering data Accessories, 208 Exhaust-air shrouds, 208 Inverter options, 207 Inverters, 205 SINVERT PVS Ordering data, 205, 207 SINVERT PVS ControlBox, 36, 39 Site of installation, 96 Standards, 198 Start screen, 142 Static grid support, 36, 38 S